APC 78-10169-02 manual Choose Start Run

Page 25

Chapter 2 Monitoring the System

Monitoring a UPS

Step 17 In the left pane of the browser window, choose Smart-UPS 1400 RM XL > PowerChute.

Step 18 In the Add Client IP Address field, enter the IP address of the SPE running System Manager.

Step 19 Click Add.

The IP address that you entered in Step 18 and Step 19 will appear in the

Configured Client IP Addresses pane.

Step 20 In the left pane of the browser window, choose Network > SNMP.

Step 21 In the SNMP table, verify that the Access field is set to enabled.

Step 22 Click Apply.

Step 23 In the Trap Receiver table, enter the UPS IP address in the Public field. Step 24 Click Apply.

Step 25 In the Access Control table, enter the UPS IP address in the Private and Public fields.

Step 26 Click Apply.

Step 27 In the left pane of the browser window, choose Event Log.

The UPS reports its status in the Event column. Text similar to the following will be displayed:

Management Card: Web User apc logged in from <IP address>

Step 28 Unplug the UPS power cord.

The UPS emits an audio tone.

Step 29 Plug the UPS power cord in again.

In the Event column of the Event Log, text similar to the following will be displayed:

UPS: Switched to battery backup power, utility power failure.

UPS: Returned from battery backup power, utility power restored.

Step 30 Choose Start > Run.

Step 31 Open a Telnet session with the SPE running System Manager: telnet IP address 5000

 

 

Cisco ICS 7750 Administration and Troubleshooting Guide

 

 

 

 

 

 

78-10169-02 Rev. B0

 

 

2-25

 

 

 

Image 25
Contents Monitoring the System Alarm Notification AlarmsHow to Access Log Messages Alarm LevelsLogging Handling Log Messages with ICS System Manager How to Read Log MessagesSaving Log Messages to a Syslog Server String Element Example Format DescriptionSeverity Levels FacilitiesKeyword Description Keyword Level Description Syslog DefinitionHow to Change the Log Configuration Configuring the Syslog Daemon on Unix Syslog Servers Default Log ConfigurationConfiguration Parameters Default Setting Changing Syslog Server Logging Task CommandSnmp Components Snmp BasicsMajor Components of SNMP-Managed Networks Snmp Management Information Base Using Snmp with MIB VariablesSnmp Network Operation DescriptionSupported MIBs Understanding TrapsCisco ICS 7750 Traps Understanding Community StringsModifying the Base Community String Monitoring with ICS System ManagerMonitoring with CiscoWorks2000 Using CiscoWorks2000 for Network ManagementCiscoWorks2000 Applications Evaluating System Performance Monitoring with Cisco IOS SoftwareSnmp and the CiscoWorks2000 Interface Evaluating Reachability and Response Times In-Band Versus Out-of-Band MonitoringEvaluating Traffic Loads Common show Commands Using show CommandsSearching and Filtering Output of show Commands Connecting and Powering Up the UPS ComponentsMonitoring a UPS Through a Serial Connection on Start Programs APC Card Management Wizard Check the Start a Web browser when finished check box Choose Start Run SetUPSHostName -HostName Name Verify that the Cisco ICS 7750 can communicate with the UPS 78-10169-02 Rev. B0