Bosch Appliances SC3100 manual Dialer ACK, Dialer Format, Digital Format

Page 23

SC3100

System Initialization

Note: For older SC3100s, the programming version required the operator to set two parameters, “Dialer ACK” and “Dialer Format” as shown below.

“Dialer ACK”:

0= Short burst 2300 Hz, short burst 1400 Hz, long burst 2300 Hz, long burst 1400Hz. 1= Short burst 2300 Hz, short burst 2300 Hz.

2= Short burst 1400 Hz, short burst 1400 Hz. 3= Long burst 2300 Hz, long burst 2300 Hz. 4= Long burst 1400 Hz, long burst 1400 Hz.

5= DTMF (ADEMCO Contact ID / 4+2 Express / High Speed).

“Dialer Format”:

0= Unknown Dialer Format or any DTMF based format. 4= 3+1 Pulse, double round.

5= 3+1 Pulse with parity.

6= Long burst 2300 Hz, long burst 2300 Hz. 4= Long burst 1400 Hz, long burst 1400 Hz.

5= DTMF (ADEMCO Contact ID / 4+2 Express / High Speed).

“Digital Format”:

Note: For newer SC3100s, please note that the programming for the newest versions required the operator to set only one parameter called "Digital Format” as shown below.

00= Either 2300 Hz or 1400 Hz ACK Tone, Any digital pulse type format.

 

01= Either 2300 Hz or 1400 Hz ACK Tone, Radionics BFSK.

 

02= Either 2300 Hz or 1400 Hz ACK Tone, 0-2 pulse type format.

 

03= Either 2300 Hz or 1400 Hz ACK Tone, 0-2 pulse type format with parity.

 

04= Either 2300 Hz or 1400 Hz ACK Tone, 3+1 pulse type format

 

05= Either 2300 Hz or 1400 Hz ACK Tone, 3+1 pulse type format with parity.

 

06= Either 2300 Hz or 1400 Hz ACK Tone, 4+2 pulse type format

 

07= Either 2300 Hz or 1400 Hz ACK Tone, 4+2 pulse type format with parity.

 

08= Either 2300 Hz or 1400 Hz ACK Tone, FBI Superfast (DTMF)

 

10= 2300 Hz ACK Tone, Any digital pulse type format.

 

11= 2300 Hz ACK Tone, Radionics BFSK.

 

12= 2300 Hz ACK Tone, 0-2 pulse type format.

 

13= 2300 Hz ACK Tone,

0-2 pulse type format with parity.

 

14= 2300 Hz ACK Tone, 3+1 pulse type format

 

15= 2300 Hz ACK Tone,

3+1 pulse type format with parity.

 

16= 2300 Hz ACK Tone, 4+2 pulse type format

 

17= 2300 Hz ACK Tone,

4+2 pulse type format with parity.

 

18= 2300 Hz ACK Tone, FBI Superfast (DTMF)

 

20= 1400 Hz ACK Tone, Any digital pulse type format.

 

21= 1400 Hz ACK Tone, Radionics BFSK.

 

22= 1400 Hz ACK Tone, 0-2 pulse type format.

 

23= 1400 Hz ACK Tone,

0-2 pulse type format with parity.

 

24= 1400 Hz ACK Tone, 3+1 pulse type format

 

25= 1400 Hz ACK Tone,

3+1 pulse type format with parity.

 

26= 1400 Hz ACK Tone, 4+2 pulse type format

 

27= 1400 Hz ACK Tone,

4+2 pulse type format with parity.

 

28= 1400 Hz ACK Tone, FBI Superfast (DTMF)

 

 

 

SC3100 Operation and Installation Guide

 

 

 

 

 

 

© 2004 Bosch Security Systems

 

Page 23

 

90026-201D

Image 23
Contents SC3100 Radio Communicator Operation and Installation GuideSC3100 Contents Contents Safecom Communications Paths Introduction Safecom Telemetry Communications SystemOverview of Safecom Radio Communicators IntroductionSC3100, Full Data Transfer, Radio Communicator Standard Radio Specifications Safecom SC3100 Radio Communicator SpecificationsFederal Communications Commission FCC Notice To Users Federal Communications Commission FCC StatementSC3100 SC3100 Circuit Board Components SC3100 Circuit BoardSystem Status LED Indications Radio Status LED Indications SC3100 DC Power Requirements of the SC3100 Radio Communicator Pre-Installation RequirementsSC3100 Pre-Installation Requirements SC3100 Wiring RequirementsAntenna Location SC3100 Radio Communicator LocationSC3100 Antenna Types SC3100 Acceptable Antenna TypesSC3100 Antenna Installation Installation ProceduresSC3100 Radio Communicator 2 R131X InstallationConnecting Wires to the SC3100 Main Molex ConnectorSystem Initialization System Initialization ProceduresProgramming Parameters Digital Format Dialer ACKDialer Format 90026-201D Bosch Security Systems Manual Initialization of an SC3100 Radio Communicator SC3100 SC3100 Programming Worksheet How to Receive Warranty Service Warranty Limited WarrantyWarranty Coverage and Duration What this Warranty does not CoverSC3100 SC3100