Panduit PN380 manual DC Wire Diagram

Page 10

PANDUIT DPoE Power System User’s Guide

Issue 1.0

 

Part Number: PN380

CAUTION:

ALWAYS FOLLOW NEC GUIDELINES AND YOUR LOCAL COMPANY PRACTICES WHEN SELECTING DC WIRING AND PROTECTION.

Table 5: Minimum Recommended DC AWG for 90° C Cabling for Unprotected Outputs shows recommended wire sizes based on ampacity. The maximum current rating for the chassis is 100 A.

1 2

14

Rectifiers

 

Single hole bulk

14 GMT Fuse

battery connections

Connections

(¼" studs)

Figure 2: DC Wire Diagram

Each chassis is equipped with 14 GMT style fuse connections and an unfused bulk DC connection located on the rear of the chassis. The GMT fused connections are made on “lugless” terminal blocks with compression screws.

The bulk DC connection may be used as a battery input or as an unfused bulk output. The connections require a terminal lug (1/4” single hole lug with a max tongue width of 0.63” or less). Size wires based on the total rectifier capacity and choose conductor size according to Table 5: Minimum Recommended DC AWG for 90° C Cabling for Unprotected Outputs .

Connecting to a DPoE Power Patch Panel

Each DPoE Power Patch Panel is shipped with a keyed power connector harness and two butt splices (PANDUIT part number BSV14X) for use in connecting the panel to the power source. The butt splices included with the DPoE Power Patch Panel will support 14 - 16 AWG solid or stranded wire.

WARNING:

Connect each DPoE Power Patch Panel to the rear of the DPoE Power System using one of the 14 GMT-fused outputs per panel.

DO NOT WIRE MULTIPLE PANELS TO A SINGLE OUTPUT ON THE DPoE POWER SYSTEM.

5

Image 10
Contents DPoE Power System User’s Guide Issue FebruaryWarranty Information Safety WarningsFCC Compliance Statement Trademarks Table of Contents Heat Dissipation Overview DPoE Power Components Available from Panduit Corporation General PracticesAC Input Wiring Package ContentsHeat Dissipation DC Output Wiring Sizing Recommended AC Circuit Breaker and Wire SizesDC Wire Diagram Connecting to a DPoE Power Patch Panel Required Tools Torque SettingsSite and Equipment Preparation AC Input Power Plant Mounting and WiringMechanical Mounting Panduit Corporation Contact InformationCord Bracket DC Output Chassis Front View GMT fuse holderEthernet Connections Power UpTest and Turn-Up RectifiersShort Circuit and Current Limit TroubleshootingTroubleshooting NIC InformationNIC Card Settings NIC Default SettingsBDT Time MNT