Short Circuit and Current Limit

ILimit can be adjusted up to +105% of the rated current of the rectifier (See Table 4: Recommended AC Circuit Breaker and Wire Sizes). The system voltage will remain constant up to ILimit at which point the system voltage will drop quickly toward 0 VDC, as shown in Figure 11: Short Circuit & Current Limit.

Once a rectifier output drops below 12 VDC for more than 5 seconds, the system will shut down. The system will automatically restart after 60 seconds, and will continue until the short circuit is cleared.

VRated

Rectifier Voltage

VShutdown

CurrentILimit

Figure 11: Short Circuit & Current Limit

Troubleshooting

The modular nature of this DPoE Power System makes diagnostics and repair easy. Make sure that all rectifiers are properly seated and latched into their respective slots. Make sure all power and signal connectors are properly mated.

Table 8: Troubleshooting

Alarm

Problem

Possible Solution

DC OK LED is extinguished

This rectifier has stopped

Rectifier failed. Replace this

 

outputting power

unit.

AC OK and all LEDs are

Commercial power has been

Reset commercial circuit

extinguished

lost to the specified rectifier(s)

breaker to the dedicated AC

 

 

circuit that feeds the system.

 

 

Seek alternative power source

 

 

until power is restored.

Fuse Open

A fuse is in the open state

Replace the open fuse

NIC Information

The PANDUIT DPoE Power System Chassis can be ordered with or without the NIC card. (PANDUIT part number DPoEPWRCM includes the NIC card. PANDUIT part number DPoEPWRCU does not). The NIC card allows the DPoE Power System to communicate with the management system. If a chassis is ordered and installed without a NIC card, it can be easily field upgraded to add the NIC card. Figure 8: Chassis (Front View) - GMT fuse holder shows where the NIC card is plugged into the chassis.

12

Image 17
Contents February DPoE Power System User’s Guide IssueFCC Compliance Statement Safety WarningsWarranty Information Trademarks Table of Contents Heat Dissipation Overview General Practices DPoE Power Components Available from Panduit CorporationHeat Dissipation Package ContentsAC Input Wiring Recommended AC Circuit Breaker and Wire Sizes DC Output Wiring SizingDC Wire Diagram Connecting to a DPoE Power Patch Panel Site and Equipment Preparation Torque SettingsRequired Tools Mechanical Mounting Power Plant Mounting and WiringAC Input Panduit Corporation Contact InformationCord Bracket Chassis Front View GMT fuse holder DC OutputTest and Turn-Up Power UpEthernet Connections RectifiersTroubleshooting TroubleshootingShort Circuit and Current Limit NIC InformationNIC Default Settings NIC Card SettingsBDT Time MNT