Panduit PN380 manual DC Output Wiring Sizing, Recommended AC Circuit Breaker and Wire Sizes

Page 9

PANDUIT DPoE Power System User’s Guide

Issue 1.0

 

Part Number: PN380

 

 

 

N+1 DC Out

Rectifiers

1

2

3

Feed 1

AC In

Feed 2

Feed 3

Figure 1: Individual AC Feed Wiring Architecture

Each individual AC feed should be protected using a circuit breaker as listed in Table 4: Recommended AC Circuit Breaker and Wire Sizes.

Table 4: Recommended AC Circuit Breaker and Wire Sizes

 

Type of

 

Number of

 

 

Part Number

Maximum

 

Maximum

 

Circuit

 

90° C

 

 

Feed

 

Rectifiers

 

 

 

Input

 

Rated AC

 

Breaker

 

Minimum

 

 

 

 

on an AC

 

 

 

Voltage

 

Current (A)

 

Minimum

 

Wire Gauge

 

 

 

 

Feed

 

 

 

 

 

 

 

value (A)

 

(AWG) to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

use at 30° C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ambient

 

 

Individual

 

 

 

 

DPoEPWRR500

90

 

7

 

15

 

14

 

 

 

1

 

 

DPoEPWRR500

180

 

3.5

 

15

 

14

 

 

AC

 

 

 

 

 

 

 

 

 

 

 

DPoEPWRR1250

90

 

17.6

 

20

 

12

 

 

Feed

 

 

 

 

 

 

 

 

 

 

 

 

 

DPoEPWRR1250

180

 

8.8

 

15

 

14

 

 

 

 

 

 

 

 

 

 

 

DC Output Wiring Sizing

There are two main considerations for sizing DC wire: ampacity and voltage drop. Ampacity refers to the safe current-carrying level as specified by U.S.-based organizations such as Underwriters Laboratories and the National Fire Prevention Association, which publishes the National Electric Code (NEC). Voltage drop is simply the amount of voltage loss in a length of wire due to ohmic resistance of the conductor. DC wire may be sized for either ampacity or voltage drop depending on branch load loop length and conductor heating. In general, ampacity considerations will drive wire selection for short loop lengths (less than 50 feet) and voltage drop will drive wire selection for long loop lengths (greater than 50 feet). The National Electric Code table 310.16 provides ampacity values for various sizes, bundles, and insulation temperature rated wire.

4

Image 9
Contents February DPoE Power System User’s Guide IssueSafety Warnings Warranty InformationFCC Compliance Statement Trademarks Table of Contents Heat Dissipation Overview General Practices DPoE Power Components Available from Panduit CorporationPackage Contents AC Input WiringHeat Dissipation Recommended AC Circuit Breaker and Wire Sizes DC Output Wiring SizingDC Wire Diagram Connecting to a DPoE Power Patch Panel Torque Settings Required ToolsSite and Equipment Preparation Mechanical Mounting Power Plant Mounting and WiringAC Input Panduit Corporation Contact InformationCord Bracket Chassis Front View GMT fuse holder DC OutputTest and Turn-Up Power UpEthernet Connections RectifiersTroubleshooting TroubleshootingShort Circuit and Current Limit NIC InformationNIC Default Settings NIC Card SettingsBDT Time MNT