PANDUIT DPoE Power System User’s Guide | Issue 1.0 |
| Part Number: PN380 |
Table 5: Minimum Recommended DC AWG for 90° C Cabling for | |||
| Unprotected Outputs | ||
|
|
|
|
| Total Rectifier Current | Wire and Lug Gauge |
|
| Rating (A) | (AWG) using 90° C wire |
|
|
| (NEC Table 310.16)1 |
|
| 10 | 16 |
|
| 20 | 14 |
|
| 25 | 12 |
|
| 30 | 12 |
|
| 40 | 10 |
|
| 50 | 8 |
|
| 75 | 6 |
|
Torque Settings
The following table shows recommended torque settings for all mechanical and electrical connections according to screw or nut size in inch pounds
Table 6: Recommended Torque Settings
Screw or Nut Size | Toque |
6 | |
12 | |
22 | |
37 | |
50 | |
65 |
Required Tools
The DPoE Power System is designed to be installed with a minimum number of commonly available tools:
•#1 & #2 flat blade and Phillips head screwdrivers
•Torque wrench
•7/16” socket, ¼” drive
•Wire and cable strippers (PANDUIT part number
•Wire and cable crimpers (such as PANDUIT part
Site and Equipment Preparation
Prior to unpacking the DPoE Power System, note any physical package damage that could indicate potential damage to the contents. After removing DPoE Power System from the boxes and packing material, inspect for shipping and/or other damage. Any problems should be reported to PANDUIT technical support.
1Table 310.16 uses Table 3B – Sizes of Conductors from BS EN 60950:2000, “Safety of Information Technology Equipment,” December 2000 for
7