RS-422 and RS-232C Cable

Section 2-2

Connecting Link Adapter AL004-(P)E

When using a Link Adapter, connect both RS-232C and RS-422 cable straight across, as shown in the following diagram. Here the SD terminal of the host com- puter, for example, is connected to the SD terminal of the Link Adapter. See 5-4 Link Adapter AL004-(P)Efor the internal configuration of the Link Adapter.

Host computer

 

Link Adapter

 

 

 

Host Link Unit

 

 

 

 

AL004-(P)E

 

 

 

 

 

 

1

FG

 

FG

1

7

FG

 

 

 

FG

7

 

 

 

7

SG

SG

7

3

SG

 

SG

3

2

SD

SD

2

9

SDA

 

SDA

9

3

RD

RD

3

5

SDB

 

SDB

5

 

 

 

 

 

6

RDA

 

RDA 6

 

 

 

 

 

1

RDB

 

RDB 1

Wiring RS-232C and RS-422 Cable Connectors

Cable Preparation

Prepare cables as follows before soldering:

1, 2, 3... 1. Cut the cable to the required length.

2.Thread the end of the cable through a boot at least 50 mm up the cable.

3.Being careful not to damage the braiding underneath, use a razor blade to cut away 25 mm of sheath for an RS-442 cable or 40 mm for an RS-232C cable.

4.Using scissors, cut away all but 10 mm of the exposed braiding.

5.Using wire strippers, remove the covering from the last 5 mm of all wires.

6.Move the boot to the cut edge of the sheath and fold the braiding back over the end of it.

7.Wrap aluminum foil tape 1 1/2 turns over the top of the braiding on top of the boot.

7

Image 17
Contents Series Link Adapters Sysmac C-series Link Adapters Page Omron Product References Page Table of Contents Precautions Intended Audience General PrecautionsSafety Precautions Application Precautions Operating Environment PrecautionsXii Introduction SectionLink Adapters NomenclatureLink Adapters General SpecificationsRepeater Units Repeater Units Wiring and Power Supply Power Supply Power Supply and Cable LengthsRS-422 and RS-232C Cable Cable LengthsSection Connecting Link Adapter AL004-PEOptical Fiber Cable APF/PCF Crystal Optical Fiber Cable AGF SpecificationsExample Backup Power SupplyUsing the Auxiliary Power Input Terminal Section Link Adapter Repeater Input Repeater Units Nomenclature and Indicator Lights Connections Dimensions System Configuration PC Link Systems AL004-PE as shown below Host Link SystemsUnits Optical Remote I/O SystemsCable Length LowWired Remote I/O Systems Dimensions and Internal Configuration Link Adapter AL001 Link Adapter AL002-PE Termination Resistance Link Adapter AL004-PECTS Selector Link Adapter AL005-PE Link Adapter AL006-PE Link Adapter AL007-P Standard Models Appendix aWire Cable Index Revision History Authorized Distributor