Omron C-series manual Wired Remote I/O Systems

Page 31

Wired Remote I/O Systems

Section 4-4

4-4 Wired Remote I/O Systems

Wired Remote I/O Master Units, Remote I/O Slave Units, and Remote Terminals can be directly connected with RS-485 cable, which has a maximum transmis- sion distance of 200 m. In order to extend the transmission distance and/or to reduce noise interference, a pair of AL007-P Link Adapters can be used to insert an optical link between any two Remote I/O Units/Remote Terminals. The follow- ing example shows two Wired Remote I/O Units connected by optical fiber cable by using a pair of AL007-P Link Adapters.

Link Adapter

AL007-P

Link Adapter

AL007-P

Optical fiber (APF/PCF)

RS-485 cable

RS-485 cable

Master, Slave, or Remote Terminal

Master, Slave, or Remote Terminal

The Link Adapters must always be used in pairs, as they convert between wire and optical signals, thereby allowing optical transmission between Units which cannot themselves be connected directly to optical fiber cable. The entire Sub- system, from Master to terminator, must be connected in series, with no branch- ing. Up to 8 Link Adapters (4 pairs) can be used for each Master. The following diagram illustrates an acceptable configuration for a Wired Remote Master Sub- system, using the maximum of 8 Link Adapters for one Master. Note that all Units are connected in series and all Link Adapters are used in pairs.

Wired Master

*

Wired Slave

 

 

 

*

 

 

 

 

Wired Slave

Link Adapter

 

AL007-P

 

 

 

 

 

 

 

 

 

 

 

*

Link Adapter

**

 

 

AL007-P

 

 

**

 

 

 

*

 

 

 

Link Adapter

 

 

AL007-P

 

 

 

 

 

 

Link Adapter

*

Link Adapter

AL007-P

 

AL007-P

 

 

 

 

 

*

 

*

 

Wired Slave

Wired Slave

 

 

 

 

*RS-485 cable

**Optical fiber (APF/PCF)

Link Adapter ** AL007-P

Link Adapter * AL007-P

Wired Slave

* Link Adapter ** AL007-P

Link Adapter * AL007-P

Terminator

Maximum cable length for any single section of optical cable is 20 m for all-plas- tic optical fiber cable (APF) and 200 m for plastic-clad optical fiber cable (PCF). To take full advantage of an optical link, shorten wire links as much as possible, even to the point of placing the Link Adapter on the same control panel as the Remote I/O Unit/Remote Terminal.

22

Image 31
Contents Series Link Adapters Sysmac C-series Link Adapters Page Omron Product References Page Table of Contents Precautions Safety Precautions General PrecautionsIntended Audience Application Precautions Operating Environment PrecautionsXii Introduction SectionLink Adapters NomenclatureRepeater Units General SpecificationsLink Adapters Repeater Units Wiring and Power Supply Cable Lengths Power Supply and Cable LengthsPower Supply RS-422 and RS-232C CableSection Connecting Link Adapter AL004-PEOptical Fiber Cable APF/PCF Crystal Optical Fiber Cable AGF SpecificationsUsing the Auxiliary Power Input Terminal Backup Power SupplyExample Section Link Adapter Repeater Input Repeater Units Nomenclature and Indicator Lights Connections Dimensions System Configuration PC Link Systems AL004-PE as shown below Host Link SystemsUnits Optical Remote I/O SystemsCable Length LowWired Remote I/O Systems Dimensions and Internal Configuration Link Adapter AL001 Link Adapter AL002-PE CTS Selector Link Adapter AL004-PETermination Resistance Link Adapter AL005-PE Link Adapter AL006-PE Link Adapter AL007-P Standard Models Appendix aWire Cable Index Revision History Authorized Distributor