| Optical Remote I/O Systems | Section |
|
Example 3 | As shown in Example 3, more than one Optical Host Link Unit can be connected | ||
|
| in series using optical fiber cables. However, if any failure (power failure, discon- | |
|
| nection, etc.) occurs in one of the Units, all the subsequent Host Link Units will | |
|
| also cease to operate. This can be prevented by using Link Adapters such as the | |
|
| ||
|
| Host Link Unit, thereby allowing the rest of the system to operate normally. In | |
|
| other words, even if a power failure occurs in a Host Link Unit connected to a | |
|
| branch line of a Link Adapter, signals are still transmitted to the other Host Link | |
|
| Units. |
Host computer | . |
|
Link Adapter
|
|
|
|
|
|
|
|
|
|
|
|
Optical fiber (APF/PCF) |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Link Adapter |
|
| Link Adapter |
| ||||
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Link Adapter |
| Link Adapter |
| ||
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Optical fiber (APF/PCF)
with
Optical Host
Link Unit
with
Optical Host
Link Unit
with
Optical Host
Link Unit
with
Optical Host
Link Unit
with
Optical Host
Link Unit
| |
Example 1 | Example 1: In an Optical System, Units can be connected in series. However, if |
| any failure (power failure, disconnection, etc.) occurs in one of the Units, all of |
the subsequent Units will also cease to operate. This can be prevented by using Link Adapters such as the
Link Adapter
Link Adapter
CPU Rack with Optical Master
Optical Link Rack
C120 CPU Rack
Optical Slave Rack
Optical fiber (APF/PCF)
C120 I/O Link Rack
20