025 16 BGU 2
123 21 HEAT 4
END OF LOOP REPORT
5.9Loop Contents
At Step 4 within the Engineer’s Menu (see Section 5.3 above), select 6:LOOP CONTENTS.
Selecting option 6 causes the display to show a list of the devices currently configured without actually
5.10Zones
WARNING: We strongly recommend that no zone editing should be attempted without the use of the pc
5.11Alarm Test
The purpose of the Alarm Test facility is for audibility testing.
At Step 4 within the Engineer’s Menu (see Section 5.3 above), select 8:ALARM TEST and follow
In this condition the control panel will automatically sound the panel and loop alarms and the internal panel buzzer for 10 seconds every 15 seconds. This will continue until key 2 is pressed or for a maximum of 15 minutes whichever occurs first.
All auxiliary outputs are disabled.
5.12Device Test (Also known as the One Man Test Mode)
At Step 4 within the Engineer’s Menu (see Section 5.3 above), select 9:DEVICE TEST.
In this condition sensors may be triggered manually. Device operation illuminates the device and LED pulses the fire LED on the panel and sounds the internal buzzer. No sounder operation, System automatically resets after 25 seconds ready for the next device test. All other outputs are disabled in this mode.
5.13Extended Menu
At Step 4 within the Engineer’s Menu (see Section 5.3 above), select 0:EXTENDED MENU.
For options available within this extended menu, see section 5.2.1 above. Use * to scroll through options.
5.14Alert Trip Level
Document Ref: Nex8inst.doc/Rev0 09.07.00 | Page 16 of 30 | Originator MC Checked by AC__ |