Nexus 21 A1557 technical specifications Document Ref Nex8inst.doc/Rev0

Page 8

DANGER: Do not incinerate batteries. If placed in a fire, the batteries may rupture, with the potential to release hazardous gases and electrolyte. VRLA batteries contain substances harmful to the environment. Exhausted batteries must be recycled. Return them to the battery manufacturer or take them to your Council tip for appropriate disposal.

We recommend that isolators are installed at both ends of each loop, immediately the loop leaves the panel.

The volt-free relay contacts provided within the panel must not be used directly to switch any voltage which exceeds 50VAC or 75VDC. (Please also refer to relay rating data).

This equipment requires a 230V AC supply. All installation work should be carried out in accordance with the recommendations of BS5839 Part 1 and the current edition of the IEE regulations by suitably qualified and trained personnel.

The panel must be earthed.

Locate the panel keys and the Installation Kit containing installation spares as follows:

2 off resistors 3K9

5 off 20mm glass fuses (assorted)

1 set of battery leads (positive, negative and a jumper lead)

Open the display door with the key provided. Carefully remove the control panel interior by releasing the cables to the display (carefully noting the connections), the top two chassis screws (located top left and right through the motherboard) and removing the lower two screws (located bottom left and right) on the chassis plate. Open the right hand door and remove chassis in similar manner.

Note: The chassis screws are bright chrome finnish

Fix the empty enclosure to the wall using the fixing hole(s) in the upper section of the enclosure. Complete the fixing operation using the remaining fixing holes in the enclosure.

Gland installation wiring into the enclosure using the cable entry points provided. Leave plugs in any unused cable entry holes.

Replace and fix the control panel chassis. Reconnect any internal earth wires.

Document Ref: Nex8inst.doc/Rev0 09.07.00

Page 8 of 30

Originator MC Checked by AC__

Image 8 Contents
Contents Exploded View and Mechanical Data/Text Identification User Controls & IndicationsDisplay Lithium Battery LBAR1 Power Supply Illustration NC1Ii A1536 8 Way Programmable Input/Output Alarm Board Loop Card Expansion MotherboardProgrammable Expansion Boards A1535 8 Way Programmable Input/Output Relay BoardImportant Notes on Batteries Document Ref Nex8inst.doc/Rev0 Number Loops Access level 1278 Overview of Engineer’s Menu OptionsAccessing Engineer’s Menu Access level 8812Setting Time & Date IsolateDevice Status Configure LoopEdit Status Disabled/Enabled ADR VAL Type STS CMDStatus To Printer Loop Contents Zones Alarm TestExtended Menu Alert Trip LevelPanel Delay Fire Trip LevelProgramming the Number of Displays Repeaters Read MemoryClear Print Queue Print Cause and Effect Data Print Memory ContentsOptions Available at Access Level Checklist Commissioning IntroductionAn Overview of the Commissioning Procedure Pre-Commissioning Wiring CheckCommissioning Procedure Alarm CircuitsCommissioning Loops Cause & Effect Testing Auxiliary CircuitsCause & Effect Editing Final CommissioningTechnical Specifications Ii Other Relevant Documentation Iii Compatible Loop Devices and Panel Responses 1XX= LED = LED Is in fire Fault Data fault AV = 0 to Operation and is