iiiCompatible Loop Devices and Panel Responses
The following table shows all devices compatible with the panel. It shows the panel’s response to events from each device type, and indicates the change in analogue value and input bits that will be displayed in the status mode. Note that some device types automatically receive cause effect outputs by default. Any such programming is indicated in the default cause and effect column.
Device type | Type | Condition | Panel response | Analogue Value | Status bits | Output bits | Default cause | Comments | |
| Code |
|
|
| (210) |
|
| and effect |
|
CEL sounder | 1 | Quiescent | None | AV = 16 | 000 | 0 | = evacuate | Bit 0 set on |
|
controller |
| Input 1 operated | Mode 1 | AV = 64 | 000 | 1 | = alert | evacuate |
|
|
| Input 2 operated | Mode 2 | AV = 48 | 000 | 2 | = relay |
|
|
|
| Input 3 operated | Remote fault | AV = 4 | 000 |
|
|
|
|
|
| Circuit fault | Remote fault | AV = 4 | 000 |
|
|
|
|
CEL Loop | 1 | Quiescent | None | AV = 16 | Echo | 0 | = evacuate | Bit 0 set on |
|
powered sounder |
| Fault | Remote fault | AV = 4 | output bits | 1 | = alert | evacuate |
|
|
|
|
|
|
| 2 | = not used |
|
|
Series 90 | 1 | Quiescent | None | AV = 16 | Echo | 0 | = evacuate | Bit 0 set on |
|
sounder/ sounder |
| Circuit fault or fault | Remote fault | AV = 4 | output bits | 1 | = alert | evacuate |
|
controller |
| input operated |
|
|
| 2 | = not used |
|
|
XP95 sounder/ | 1 | Quiescent | None | AV = 16 | Echo | 0 | = evacuate | Bit 0 set on |
|
sounder |
| Circuit fault | Remote fault | AV = 4 | output bits | 1 | = alert | evacuate |
|
controller |
|
|
|
|
| 2 | = not used |
|
|
CEL I/O unit | 2 | Quiescent | None | AV = 16 | 000 | 0 | = relay 1 |
|
|
|
| Input 1 operated | Fire | AV = 64 | 000 | 1 | = relay 2 |
|
|
|
| Input 2 operated | Input | AV = 48 | 000 | 2 | = relay 3 |
|
|
|
| Input 3 operated or | Remote fault | AV = 4 | 000 |
|
|
|
|
|
| power supply failed |
|
|
|
|
|
|
|
Series 90 | 2 | Quiescent | None | AV = 16 | 000 | 0 | = relay 1 |
| X means status |
I/O unit |
| Input 1 operated | Fire | AV = 16 | 1XX | 1 | = relay 2 |
| does not affect |
|
| Input 2 operated | Input | AV = 16 | 01X | 2 | = relay 3 |
| panel status |
|
| Input 3 operated | Remote fault | AV = 16 | 001 |
|
|
|
|
Document Ref: Nex8inst.doc/Rev0 09.07.00 | Page 26 of 30 Originator MC Checked by AC___Approved by JBJ__ |