Refer to the Installation & Commissioning Manuals for these boards.
6.6Auxiliary Circuits
Any auxiliary circuits or equipment which is not supplied as a standard part of the fire alarm panel is the responsibility of the installer and must be tested for safe and correct operation by the commissioning engineer. If special output facilities are provided as extra equipment, refer to separate drawings and manuals for commissioning information.
6.7Cause & Effect Editing
The Nexus panel may now be programmed with the text, zone and cause & effect information.
WARNING: We strongly recommend that no cause & effect programming should be attempted without the use of the pc
6.7.1Cause & Effect Testing
Testing of the panel’s fire and fault relays and all cause & effect outputs must be done with the system fully functional. There are two options:
(i)Operate field devices and physically check programmed output devices for correct operation.
(ii)Select engineer’s option 5: STATUS and operate devices with the System Enabled option as described in the Nexus
6.8Final Commissioning
6.8.1Select engineer’s Option 9: DEVICE TEST and carry out tests on all sensor devices.
6.8.2Testing of the panel’s fire and fault relays and all cause & effect outputs must be done with the system fully functional.
There are two options for testing the panels cause & effect:
(i)Operate devices as required
(ii)Use engineer’s Option 5: STATUS, selection 1 SYSTEM ENABLED to operate devices
Document Ref: Nex8inst.doc/Rev0 09.07.00 | Page 23 of 30 | Originator MC Checked by AC__ |