Nexus 21 A1557 technical specifications Power Supply Illustration, NC1

Page 5

A1557 Field Terminal List [Listed along the top edge of the PCB from left to right]

Terminal Ident.

Function

Terminal Ident.

Function

 

Aux Fire

NO 1

Fire

relay normally open 1

Alarm 1

+

Sounder circuit 1 + [Active polarity]

 

NC1

Fire

relay normally closed 1

 

-

Sounder circuit 1 -

[Active polarity]

 

P1

Fire

relay pole 1

Alarm 2

+

Sounder circuit 2 + [Active polarity]

 

NO 2

Fire

relay normally open 2

 

-

Sounder circuit 2 -

[Active polarity]

 

NC2

Fire relay normally closed 2

Network

NO +

Panel network out +

 

P2

Fire

relay pole 2

 

NO-

Panel network out -

 

Aux Flt

P

Fault relay pole

 

NI +

Panel network in +

 

 

NO

Fault relay normally open

 

NI -

Panel network in -

 

 

NC

Fault relay normally closed

Loop 1

LO+

Loop 1 out +

 

Aux

24V

Aux DC supply [24V]

 

LO-

Loop 1 out -

 

 

0V

Aux DC supply [0V]

 

LI+

Loop 1 in +

 

I/O

MX+

Local I/O expansion port +

 

LI-

Loop 1 in -

 

 

MX-

Local I/O expansion port -

Loop 2

LO+

Loop 2 out +

 

Repeater

RO +

Repeater out +

 

LO-

Loop 2 out -

 

 

RO -

Repeater out -

 

LI+

Loop 2 in +

 

 

RI +

Repeater in +

 

LI-

Loop 2 in -

 

 

RO -

Repeater in -

 

 

 

 

Remote

SAL

Silence alarms

 

 

 

 

Inputs

RST

Reset

 

 

 

 

 

 

 

 

 

 

EVC

Evacuate

 

 

 

 

 

SBZ

Silence buzzer

 

 

 

 

 

COV

Class change alarm

 

 

 

 

 

FLT

Fault

 

 

 

 

 

1.1.6Power Supply Illustration

+

+

12V

12V

Document Ref: Nex8inst.doc/Rev0 09.07.00

Page 5 of 30

Originator MC Checked by AC__

Image 5
Contents Contents User Controls & Indications Exploded View and Mechanical Data/Text IdentificationDisplay LBAR1 Lithium BatteryNC1 Power Supply IllustrationLoop Card Expansion Motherboard Ii A1536 8 Way Programmable Input/Output Alarm BoardProgrammable Expansion Boards A1535 8 Way Programmable Input/Output Relay BoardImportant Notes on Batteries Document Ref Nex8inst.doc/Rev0 Number Loops Overview of Engineer’s Menu Options Access level 1278Access level 8812 Accessing Engineer’s MenuIsolate Setting Time & DateDevice Status Configure LoopEdit ADR VAL Type STS CMD Status Disabled/EnabledStatus To Printer Zones Alarm Test Loop ContentsExtended Menu Alert Trip LevelFire Trip Level Panel DelayProgramming the Number of Displays Repeaters Read MemoryClear Print Queue Print Cause and Effect Data Print Memory ContentsOptions Available at Access Level Commissioning Introduction ChecklistPre-Commissioning Wiring Check An Overview of the Commissioning ProcedureCommissioning Procedure Alarm CircuitsCommissioning Loops Auxiliary Circuits Cause & Effect TestingCause & Effect Editing Final CommissioningTechnical Specifications Ii Other Relevant Documentation 1XX Iii Compatible Loop Devices and Panel Responses= LED = LED Is in fire Fault Data fault AV = 0 to Operation and is