Device type | Type | Condition | Panel response | Analogue Value | Status bits | Output bits | Default cause | Comments | |
| Code |
|
|
| (210) |
|
| and effect |
|
Series 90 zone | 4 | Quiescent | None | AV = 16 | Echo | 0 | = reset | Bit 0 set on | Program LED |
monitor |
| Fire | Fire | AV = 64 | output bits | 1 | = test | reset or clear | bit in cause |
|
| Circuit fault | Remote fault | AV = 4 |
| 2 | = LED | faults | effect if required |
Series 90 control | 4 | Quiescent | None | AV = 16 | Echo | 0 | = fault test | Bit 0 set on | Program LED |
unit monitor |
| Alarm | Fire | AV = 64 | output bits | 1 | = alarm test | reset or clear | bit in cause |
|
| Circuit fault | Remote fault | AV = 4 |
| 2 | = remote LED | faults | effect if required |
XP95 Mini- | 4 | Quiescent | None | AV = 16 | Echo | 0 | = fault test | Bit 0 set on | Program LED |
switch monitor |
| Alarm | Fire | AV = 64 | output bits | 1 | = alarm test | reset or clear | bit in cause |
|
| Alert | Alert | AV = 45 - 51 |
| 2 | = LED | faults | effect if required |
|
| Circuit fault | Remote fault | AV = 4 |
|
|
|
|
|
XP95 Switch | 4 | Quiescent | None | AV = 16 | Echo | 0 | = not used | Bit 0 set on | Program LED |
monitor |
| Alarm | Fire | AV = 64 | output bits | 1 | = alarm test | reset or clear | bit in cause |
|
| Alert | Alert | AV = 45 - 51 |
| 2 | = LED | faults | effect if required |
|
| Circuit fault | Remote fault | AV = 4 |
|
|
|
|
|
XP95 Switch | 4 | Quiescent | None | AV = 16 | Echo | 0 | = | Bit 0 set on | Program LED |
monitor plus |
| Alarm | Fire | AV = 64 | output bits | 1 | = alarm test | reset or clear | bit in cause |
|
| Alert | Alert | AV = 45 - 51 |
| 2 | = LED | faults | effect if required |
|
| Circuit fault | Remote fault | AV = 4 |
|
|
|
|
|
XP95 Zone | 4 | Quiescent | None | AV = 16 | Echo | 0 | = reset | Bit 0 set on | Program LED |
Monitor |
| Alarm | Fire | AV = 64 | output bits | 1 | = alarm test | reset or clear | bit in cause |
|
| Circuit fault | Remote fault | AV = 4 |
| 2 | = LED | faults | effect if required |
XP95 control unit | 4 | Quiescent | None | AV = 16 | Echo | 0 | = reset | Bit 0 set on | Program LED |
monitor |
| Alarm | Fire | AV = 64 | output bits | 1 | = alarm test | reset or clear | bit in cause |
|
| Circuit fault | Remote fault | AV = 4 |
| 2 | = LED | faults | effect if required |
XP95 Radio | 4 | Quiescent | None | AV = 16 | Echo | 0 | = reset | Bit 0 set on |
|
Interface |
| Alarm | Fire | AV = 64 | output bits | 1 | = alarm test | reset or clear |
|
|
| Circuit fault | Remote fault | AV = 4 |
| 2 | = LED | faults |
|
Document Ref: Nex8inst.doc/Rev0 09.07.00 | Page 28 of 30 | Originator MC Checked by AC__ |