Device type | Type | Condition | Panel response | Analogue Value | Status bits | Output bits | Default cause | Comments | |
| Code |
|
|
| (210) |
|
| and effect |
|
Series 90 | 2 | Quiescent | None | AV = 8 to 44 | 000 | 0 | = relay 1 |
| X means status |
I/O analogue unit |
| Input 1 operated | Fire | AV = 55 to 127 | 1XX | 1 | = relay 2 |
| does not affect |
|
| Input 2 operated | Input | AV = 45 to 54 | 01X | 2 | = relay 3 |
| panel status. |
|
| Input 3 operated | Remote fault | AV = 0 to 7 | 001 |
|
|
| See note 2. |
Series 90 | 2 | Quiescent | None | AV = 16 | 000 | 0 | = relay |
|
|
I/O unit |
| Input operated | Fire | AV = 16 | 001 | 1 | = not used |
|
|
|
|
|
|
|
| 2 | = not used |
|
|
Series 90 switch | 2 | Quiescent | None | AV = 16 | 000 | 0 | = remote |
|
|
monitor unit |
| Input operated | Fire | AV = 16 | 100 | indicator |
|
| |
|
|
|
|
|
| 1 | = not used |
|
|
|
|
|
|
|
| 2 | = not used |
|
|
XP95 I/O unit | 2 | Quiescent | None | AV = 16 | 000 | 0 | = remote |
| Fire overrides |
|
| Input operated | Fire | AV = 16 | 1X0 | indicator |
| input which in | |
|
| Opto input active | Input | AV = 16 | 010 | 1 | = not used |
| turn overrides |
|
| Input fault | Remote fault | AV = 4 | 000 | 2 | = not used |
| remote fault |
|
|
|
|
|
|
|
|
|
|
XP95 output unit | 2 | Quiescent | None | AV = 16 | 000 | 0 | = relay |
|
|
Series 90 | 3 | Quiescent | None | AV = 8 to 44 | Echo | 0 | = remote LED | Bit 0 and bit 2 | See note 1. |
ionisation smoke |
| Fire | Fire | AV = 55 to 127 | output bits | 1 | = self test | set when device |
|
|
| Alert | Alert | AV = 45 to 54 |
| 2 | = LED | is in fire |
|
|
| Fault | Data fault | AV = 0 to 7 |
|
|
|
|
|
XP95 ionisation | 3 | Quiescent | None | AV = 8 to 44 | Echo | 0 | = remote LED | Bit 0 and bit 2 | See note 1. |
smoke |
| Fire | Fire | AV = 55 to 127 | output bits | 1 | = self test | set when device |
|
|
| Alert | Alert | AV = 45 to 54 |
| 2 | = LED | is in fire |
|
|
| Fault | Data fault | AV = 0 to 7 |
|
|
|
|
|
CEL zone | 4 | Quiescent | None | AV = 16 | 000 | 0 | = relay 1 | Bit 0 set on |
|
monitor |
| Input 1 operated | Fire | AV = 64 | 000 | 1 | = relay 2 | reset or clear |
|
|
| Input 2 operated | Alert | AV = 48 | 000 | 2 | = relay 3 | faults |
|
|
| Input 3 operated | Remote fault | AV = 4 | 000 |
|
|
|
|
Document Ref: Nex8inst.doc/Rev0 09.07.00 | Page 27 of 30 | Originator MC Checked by AC__ |