MGE UPS Systems 66074, 66244, 66846 user manual 20/69

Page 20

www.mgeups.com

Network

Management Cards

User Manual

ZRestart after is the minimum shutdown time before restarting the UPS after a shutdown sequence. It is thus possible to limit repeated restarts that may be due to several successive utility failures.

ZIf the Battery is charged for and If Capacity exceeds are two extra conditions for minimum battery level and maximum recharge time to be reached before restarting the UPS after utility restoration

For controlled outlets (group 1 or group 2 ), the page enables programming of operation time and level in backup mode to manage outlet load shedding in the event of electric power failure:

ZSwitch Off after (from 0 to 65534).defines the time during which the outlet is supplied starting from the moment of utility failure. Caution, this time includes the outlet shutdown duration.

ZSwitch Off if capacity under is an extra condition for outlet shutdown that can trigger the shutdown sequence before shutdown duration runs out.

ZShutdown duration is the time required for complete shutdown of the systems supplied by the outlet when an outlet shutdown sequence is launched.

It is calculated automatically using the maximum shutdown durations of subscribed clients.

ZSwitch On (from 0 to 65534). is the period between main output startup and startup of the relevant programmable outlet, therefore outlet startup can be delayed in relation to the main output.

Security: The administrator has to click on Save and enter his login/password to save any modifications. The

default login and password are: MGEUPS

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Network Management Card – User Manual

34003676EN/GA

Page 20/69

Image 20
Contents E U N I N T E R R U P T I B L E P O W E R P R O V I D E R Table of Contents Network Management CardsConfiguration Configuration VIA Telnet Configuration VIA SSHMaintenance Software UPGRADE62 APPENDICES63 Tables of Alarms and EventsMGE Network Solution Connecting the UPS to the NetworkIntroduction Network Management Card or ProxyMGE supervisor Enterprise Power Manager Protecting the computers / serversMonitoring the UPSs over the network Network Shutdown modulePresentation of the Environment Sensor solution How to connect UPS / agent / networkSetting up the protection ConnectionSending text messages SMS Compatibility with the legacy Solution-Pac WAN offeringDirect sending of E-mail Technical data 9/69 Installation and Configuration InstallationBasic configuration Environment SensorSupervision / Administration via a Web browser Optimising the performance of your browserUPS UPS propertiesUPS zone general information on the UPS UPS status zone essential informationBattery status zone On-line help 3 3-Phase display Normal input measurementsBy Pass measurements Battery measurementsUPS Control 17/69 UPS weekly schedule programming Shutdown parameters Important note20/69 Viewing the alarms Logs Measurements23/69 Event log System log Notified events NotificationEmail Notification Mail message configuration see next Recipient ListSubject Email Message SettingsSender 29/69 Configuration User Name and password by default are MgeupsNetwork Settings 32/69 System 34/69 Notified Applications Central Shutdown Configuration Access control 38/69 SSL Time Environment CharacteristicsStatus Configuration Log Environment status Environment Settings Humidity4 Log Shutdown criteria managed by the Management Card Servers protectionSet-up of the shutdown parameters Specific set-up for long autonomy installation 30 mn Shutdown when backup time is less thanControlled outlets Shutdown durationLoad shedding or sequential shutdown Sequential startupProgrammable outlet Different server and UPS shutdown sequencesMain UPS outlet 49/69 2.3 Programmable outlet 2.1 Main UPS outlet2.2 Programmable outlet 51/69 3.1 Main UPS outlet 3.2 Programmable outletNetwork 4 Off/On command Main outlet55/69 Configuration in local mode Configuring a set of cards with MupgradeConfiguration in local mode and via Telnet or SSH Choice 1 Snmp agent configuration menu MgeupsChoice 3 Access control Choice 2 UPS parametersChoice 4 Restore default configuration Choice 5 Reset the cardPuTTY SSH Client Program Configuration via TelnetConfiguration via SSH 61/69 Maintenance Software upgradeCard firmware upgrade using Mupgrade Windows Card software upgrade via Tftp Unix and WindowsTables of alarms and events Alarm tableAppendices UPS event tableUPS 65/69 System alarm table English FrenchGlossary Telnet Programmable outlet controlled outletSubnet mask Trap Snmp UM-Client

66074, 66244, 66846 specifications

MGE UPS Systems, a renowned leader in the uninterruptible power supply (UPS) sector, offers a range of products designed to deliver reliable power protection for critical applications. Among their notable models are the MGE UPS Systems 66846, 66244, and 66074, each offering unique features, advanced technologies, and robust characteristics tailored for various operational needs.

The MGE UPS Systems 66846 is characterized by its high efficiency and modular design, making it suitable for a wide array of environments. This model incorporates advanced power management capabilities, which ensures that users benefit from enhanced energy savings while maintaining optimal performance. With a scalable architecture, the 66846 can adapt to evolving power requirements, providing users with the flexibility to expand their system as their needs grow. The model also includes intelligent battery management features that prolong battery life and enhance reliability.

Moving to the MGE UPS Systems 66244, this model stands out for its compact design and high power density. It is engineered to deliver superior electrical performance while occupying minimal space, making it an excellent choice for facilities with limited room for equipment. The 66244's advanced thermal management system ensures that the device operates efficiently under varying load conditions without overheating. Its intuitive user interface simplifies monitoring and managing the UPS, giving users real-time insights into operational status and alerts.

The MGE UPS Systems 66074 offers advanced features geared towards critical infrastructure in data centers and telecom applications. This model boasts high fault tolerance and redundancy mechanisms, ensuring continuous power delivery even in the event of component failure. The 66074 is equipped with cutting-edge digital signal processing technology, which enhances the performance and reliability of the power supply. Additionally, it supports various connectivity options, allowing for seamless integration with existing power management systems.

Across these models, MGE UPS Systems emphasize user-friendliness with intuitive control interfaces and remote monitoring capabilities. Furthermore, their commitment to sustainability is evident in the energy-efficient designs that reduce the overall carbon footprint of power management operations. Each unit is rigorously tested to adhere to international safety and performance standards, ensuring confidence in their reliability for critical applications. Overall, MGE UPS Systems 66846, 66244, and 66074 represent a blend of innovation, efficiency, and dependability in the UPS market, making them ideal choices for businesses looking to safeguard their operations against power interruptions.