c.Disconnect the Phase B hot wire from the AC power source and place it through the hole in the Current Sensor such that the arrow on the Current Sensor points towards the AC power source. Then, reattach the Phase B hot wire to the AC power source.

Step 4: Install the third Current Transformer as follows:

a.Connect the black wire to pin 11 (IC+) on the ACM100

b.Connect the white wire to pin 12 (IC-) on the ACM100

c.Disconnect the Phase C hot wire from the AC power source and place it through the hole in the Current Sensor such that the arrow on the Current Sensor points towards the AC power source. Then, reattach the Phase C hot wire to the AC power source.

Step 5: You must supply a cable for connecting the voltage sense pins on the ACM100 to the AC source. For the purposes of these instructions, we will assume that the cable has one black conductor and one white conductor. Install the voltage sense cable as follows:

a.Connect the white wire from one end of the Voltage Sense cable to pin 4 (VANeutral) on the ACM100.

b.Connect the white wire from the other end of the Voltage Sense cable to the neutral wire of the AC source being monitored.

c.Connect the black wire from one end of the Voltage Sense cable to pin 1 (VALine) on the ACM100

d.Connect the black wire from the other end of the Voltage Sense cable to a fuse appropriately sized for the black wire (18 gauge wire minimum and 3 amp fuse or less).

e.Connect the other end of the fuse to the AC source hot wire (the fuse should be placed within 6 inches of the connection to the hot wire).

Step 6: Install the second Voltage Sense cable as follows:

a.Connect the white wire from one end of the second Voltage Sense cable to pin 5 (VBNeutral) on the ACM100.

b.Connect the white wire from the other end of the second Voltage Sense cable to the neutral wire of the AC source being monitored.

c.Connect the black wire from one end of the second Voltage Sense cable to pin 2 (VBLine) on the ACM100

d.Connect the black wire from the other end of the second Voltage Sense cable to a fuse appropriately sized for the black wire (18 gauge wire minimum and 3 amp fuse or less).

e.Connect the other end of the fuse to the AC source hot wire (the fuse should be placed within 6 inches of the connection to the hot wire).

Step 7: Install the third Voltage Sense cable as follows:

a.Connect the white wire from one end of the second Voltage Sense cable to pin 6 (VCNeutral) on the ACM100.

b.Connect the white wire from the other end of the second Voltage Sense cable to the neutral wire of the AC source being monitored.

Revision 1.2

Page 9

Image 13
Contents Page RevisionRevision Copyright 2012 Maretron, LLP All Rights Reserved Maretron, LLP 9014 N. 23rd Ave #10ACM100 User’s Manual Revision HistoryPage RevisionTable of Figures Table of ContentsSingle-Phase Dual Line Connection Diagram Table of AppendicesThree-Phase Connection Diagram Mounting Surface Template1 Introduction 1.2 ACM100 Features1.1 Firmware Revision 1.3 Quick Install 2 Installation2.1 Unpacking the Box 2.2 Choosing a Mounting Location2.3 Mounting the ACM100 2.4 Connecting the ACM1002.4.1 NMEA 2000 Connection 2.4.2 AC Sensor Connections Pin # Signal NameConnection AC Source 2.4.2.1 Single-Phase Phase A Connection2.4.2.2 Single-Phase Phase A, B Connection Page Figure 5 - Three-Phase Connection Diagram 2.4.2.3 Three-Phase Phase A, B, C ConnectionPage 2.4.3 Checking Connections 2.5 Configuring the ACM1002.5.1 Device Instance 2.5.2 AC Device Type2.5.5 Advanced Configuration… 2.5.4 Reset Total Energy Recorded2.5.5.3 Power Damping Period 2.5.3 AC Circuit Type2.5.7 Restore Factory Defaults 2.5.6 NMEA 2000 PGN Enable/Disable3 Output Parameters 2.5.5.5 Current Transformer B3.1 Line-Specific and Line-to-Neutral Measurements 4 Maintenance3.2 Line-to-Line Measurements Symptom 5 TroubleshootingTroubleshooting Procedure Certifications 6 Technical SpecificationsNMEA 2000 Parameter Group Numbers PGNs Default RateElectrical 7 Technical SupportMechanical EnvironmentalFigure 6 - Mounting Surface Template 8 Installation TemplateWarranty Return Procedure 9 Maretron 2 Year Limited WarrantyACM100 NMEA 2000 Periodic Data Transmitted PGNs Appendix A - NMEA 2000 InterfacingAppendix A - NMEA 2000 Interfacing Page A1PGN 65005 - Utility Total AC Energy Page A2