Liebert SmartSwitchTM Input and Output Power Connections, Wire Size Tightening Torque, Lb.-in N-m

Page 10

2.2Input and Output Power Connections

All wiring should be installed by a qualified electrician. All wiring must comply with NEC and applicable local codes.

! WARNING

RISK OF ELECTRICAL SHOCK. HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE SMARTSWITCH. VERIFY THAT THE ALL INPUT POWER SOURCES ARE DE-ENERGIZED AND LOCKED OUT BEFORE MAKING CONNECTIONS INSIDE THE UNIT. THE SMARTSWITCH IS INTENDED TO BE FED FROM TWO SOURCES. BE SURE ALL SOURCES OF POWER ARE DE- ENERGIZED AND LOCKED OUT BEFORE MAKING CONNECTIONS INSIDE THE UNIT.

! WARNING

RISK OF UNIT DAMAGE. THE SMARTSWITCH IS INTENDED TO BE OPERATED FROM SOLIDLY GROUNDED POWER SOURCES. OPERATION FROM OTHER THAN SOLIDLY GROUNDED POWER SOURCES MAY CAUSE MISOPERATION OR DAMAGE TO THE UNIT.

If the unit is not furnished with input power cables, then input power connections are made to terminal blocks located inside the unit. Refer to the unit outline drawings furnished with the unit or Figure 2 and Figure 3 for the location of the input power connections. Terminal blocks for switches rated 13 to 20 amps accept wires sizes of #14 to #10 AWG. Terminal blocks for switches rated 25 to 60 amps accept wire sizes of #12 to #6 AWG.

Wire Size

Tightening Torque

AWG

Lb.-in (N-m)

#14 - #10

20 (2.3)

 

 

#8

25 (2.9)

 

 

#6

35 (4.0)

 

 

6 Unpacking and Installation

Image 10
Contents SmartSwitch Power ProtectionPage Table of Contents Figures Important Safety Instructions Specifications IntroductionElectrical Specifications Designation Phase Neutral Gnd Poles Amps Type Refer to SmartSwitch RatingsConnector Receptacle Voltage No. of Conductors EnclosureUnpacking and Installation Location ConsiderationsWire Size Tightening Torque Input and Output Power ConnectionsLb.-in N-m 17.25 18.5 469 Typical 25 to 60 Amp SmartSwitch Underfloor / Wallmount Unit Typical Input and Output Power Connections Control Wiring Connections GroundingSmartSwitch Status Indicators Description of SmartSwitch OperationStatus Indicators Indicator DescriptionRS-232 Communications Port RS-232 Ascii Communication Port Customer CommandsExample View Status Response Example View Event Log Response Example View Settings ResponseLogged Events include Bypass/Transfer Control Switch Operator ControlsOperating Guidelines Operating Guidelines Maintenance Maintenance Automatic Transfer Switch Technical Support