Liebert SmartSwitchTM Typical 25 to 60 Amp SmartSwitch Underfloor / Wallmount Unit

Page 12

Figure 3 Typical 25 to 60 Amp SmartSwitch Underfloor / Wallmount Unit

If the unit is furnished with input power cables, the input power connections are made to the receptacles matching the input power plugs furnished located in close proximity to the Smart- Switch (typically within 3 feet).

The input power connections to the SmartSwitch must include overcurrent protection included as part of the supply power distribution system. The maximum supply overcurrent protection for each SmartSwitch input should not exceed 125% of the rated continuous current or as indicated on the unit label. The maximum size overcurrent protection device (fuse or circuit breaker) for the particular SmartSwitch used is listed in the unit ratings table (see Table 1).

The nominal voltage and frequency of each input source must match the voltage rating indicated on the unit label. Failure to comply with this requirement may result in misoperation or damage to the unit.

Severe input voltage distortion or large ringing transients, such as those caused by utility capaci- tor switching, may be interpreted by the SmartSwitch as a source failure.

The SmartSwitch is intended to be supplied from two independent AC power sources to provide protection against a source failure.

8 Unpacking and Installation

Image 12
Contents SmartSwitch Power ProtectionPage Table of Contents Figures Important Safety Instructions Specifications IntroductionElectrical Specifications SmartSwitch Ratings Connector Receptacle Voltage No. of ConductorsDesignation Phase Neutral Gnd Poles Amps Type Refer to EnclosureUnpacking and Installation Location ConsiderationsInput and Output Power Connections Wire Size Tightening TorqueLb.-in N-m 17.25 18.5 469 Typical 25 to 60 Amp SmartSwitch Underfloor / Wallmount Unit Typical Input and Output Power Connections Control Wiring Connections GroundingDescription of SmartSwitch Operation Status IndicatorsSmartSwitch Status Indicators Indicator DescriptionRS-232 Ascii Communication Port Customer Commands RS-232 Communications PortExample View Status Response Example View Settings Response Example View Event Log ResponseLogged Events include Bypass/Transfer Control Switch Operator ControlsOperating Guidelines Operating Guidelines Maintenance Maintenance Automatic Transfer Switch Technical Support