Liebert SmartSwitchTM operation manual RS-232 Communications Port, Example View Status Response

Page 16

3.3RS-232 Communications Port

The SmartSwitch contains an RS-232 ASCII communications port for changing user settings and remote monitoring of unit status and alarm information. The RS-232 port connections are to a

9-pin “D” connector located on the outside of the unit. See Figure 2 and Figure 3 for the location of the port and Figure 5 for the port connections.

The default parameters of the communications port are RS-232 terminal emulator protocol using EIA voltage levels, ASCII Characters, Half Duplex Asynchronous Communications, 9600 Baud rate, 8 Data Bits, 1 Stop Bit, No Parity, No Handshaking, and <CR> Terminator.

The port uses a query-response format. Commands are divided into two groups, inquiries and set- tings changes. The list of available customer commands is shown in Table 3. Only one command is serviced at a time. A password is required to change unit settings. The default password is “Lie- bert.” Inquiries include viewing unit status, viewing event history log, and viewing settings. Typi- cal inquiry responses are shown in Table 4, Table 5, and Table 6.

The Event Log contains the last 175 switch events. The Settings Log contains the last 50 switch settings changes.

Table 3

RS-232 ASCII Communication Port Customer Commands

 

 

 

 

 

Function

Command

Selections

View Status

Y<CR>

 

View Event Log

B<CR>

Views up to the last 175 switch events

View Settings

O<CR>

 

Set Time*

 

Thh:mm:ss<CR>

hh = hours, mm = minutes, ss = seconds

Set Date*

 

Dmm/dd/yy<CR>

mm = month, dd = day, yy = year

 

 

 

Synchronization Window*

Pn<CR>

n = 1 to 20 degrees

Auto Retransfer Enable*

Rx<CR>

x = 0 for disabled, x = 1 for enabled

Auto Retransfer Delay*

En<CR>

n = 1 to 60 seconds

Load Current Transfer Inhibit*

In<CR>

n = 1 to 10 times full load current

 

 

 

Load Current Inhibit Reset*

Hx<CR>

x = 0 for Manual, x = 1 for Automatic

Auto Transfer Test Enable*

Sx<CR>

x = 0 for disabled, x = 1 for enabled

Auto Transfer Test Settings*

Xmm/dd/yy hh:mm:ss n<CR>

mm/dd/yy = test date, hh:mm:ss = test time,

 

 

 

n = 1 to 365 days between tests

Restore Default Settings*

W<CR>

 

Clear Event Log*

G<CR>

 

View Settings Log

C<CR>

Views up to the last 50 switch settings

 

 

 

changes

Clear Settings Log*

Z<CR>

 

 

 

 

 

*User Password required for these commands. System prompts for password entry. Password remains valid for 2 minutes after each password-required command.

Table 4 Example View Status Response

ALARMS

Power Supply Fault

SOURCE and SWITCH

Load on Preferred Source

Switch in Normal Mode

Preferred Source Available

Alternate Source Available

Alarms include:

Preferred Source Fail, Alternate Source Fail, Out of Sync, Transfer Inhibit, Peak Overload, Transfer Test Failed, and Power Supply Fault.

Source and Switch Messages include:

Load on Preferred Source, Load on Alternate Source, Switch in Normal Mode, Manual Transfer to S1, Manual Transfer to S2, Bypass to S1, Bypass to S2, Preferred Source Available, and Alternate Source Available.

12 Operating Instructions

Image 16
Contents SmartSwitch Power ProtectionPage Table of Contents Figures Important Safety Instructions Specifications IntroductionElectrical Specifications SmartSwitch Ratings Connector Receptacle Voltage No. of ConductorsDesignation Phase Neutral Gnd Poles Amps Type Refer to EnclosureUnpacking and Installation Location ConsiderationsWire Size Tightening Torque Input and Output Power ConnectionsLb.-in N-m 17.25 18.5 469 Typical 25 to 60 Amp SmartSwitch Underfloor / Wallmount Unit Typical Input and Output Power Connections Control Wiring Connections GroundingDescription of SmartSwitch Operation Status IndicatorsSmartSwitch Status Indicators Indicator DescriptionRS-232 Communications Port RS-232 Ascii Communication Port Customer CommandsExample View Status Response Example View Event Log Response Example View Settings ResponseLogged Events include Bypass/Transfer Control Switch Operator ControlsOperating Guidelines Operating Guidelines Maintenance Maintenance Automatic Transfer Switch Technical Support