3.0OPERATING INSTRUCTIONS
NOTE
Read the entire operating instructions section before placing the
SmartSwitch into operation.
NOTE
For continued protection against a source failure, periodic testing of the SmartSwitch is recommended. For manual testing, see the transfer control instructions.
3.1Description of SmartSwitch Operation
The SmartSwitch™ is an automatic transfer switch designed to provide fast automatic transfers between two independent, synchronous AC power sources to provide continuity of AC power to critical equipment, such as information technology equipment. One of the two AC inputs is desig- nated as the “preferred” source to which the SmartSwitch will connect the load as long as the des- ignated input source is within acceptable voltage limits. If the preferred source falls outside the acceptable limits, the SmartSwitch is designed to transfer the output load to the other “alternate” input source, as long as the alternate source is within acceptable voltage limits and is synchro- nized with the preferred source within the selected phase synchronization window. The Smart- Switch provides fast,
The SmartSwitch™ consists of two modules, a fixed module containing the input and output con- nections and bypass/transfer control switch, and a
3.2Status Indicators
The SmartSwitch contains seven
Table 2 | SmartSwitch Status Indicators | |
|
|
|
| Indicator | Description |
ON PREFERRED SOURCE | The output load is connected to the preferred source. | |
ON ALTERNATE SOURCE | The output load is connected to the alternate source. | |
PREFERRED SOURCE OK | All phases of the preferred source are within voltage limits. | |
ALTERNATE SOURCE OK | All phases of the alternate source are within voltage limits. | |
TRANSFER INHIBITED | Automatic transfer is inhibited. Reasons for transfer (or retransfer) inhibit | |
|
| include both sources are not available, sources are not synchronized, or the |
|
| output load has exceeded the preset limit. |
SUMMARY ALARM | The SmartSwitch has detected a fault condition. If both sources are available | |
|
| and synchronized, then the alarm may indicate a SmartSwitch failure. |
ON BYPASS | The bypass/transfer switch is in the bypass position. | |
S1 PREFERRED* | Source 1 is selected as the preferred source. | |
S2 PREFERRED* | Source 2 is selected as the preferred source. |
*These LED indicators are only provided on the rackmount units.
Operating Instructions | 11 |