Liebert SmartSwitchTM operation manual Electrical Specifications

Page 7

1.1.2Electrical Specifications

Nominal input voltage

120 or 208 volts single phase 2W+G, 60 Hz 220, 230, or 240 volts single phase 2W+G, 50 Hz 208/120 volts single phase 3W+G, 60 Hz

208 volts three phase, 3W+G, 60 Hz 208/120 volts three phase, 4W+G, 60 Hz

380, 400, or 415 volts three-phase 3W+G, 50 Hz

380/220, 400/230, or 415/240 volts three phase 4W+G, 50 Hz Solidly grounded power sources

Branch circuit breaker rating 15, 20, 30, or 60 amps, 60 Hz 13, 25, or 50 amps, 50 Hz

Maximum continuous current 12, 16, 24, or 48 amps, 60 Hz 13, 25, or 50 amps, 50 Hz

Load power factor range: 0.5 to 1.0, leading or lagging.

Load crest factor: up to 3.5.

Source voltage distortion: up to 10% THD.

Overload capability: 125% of continuous current for 2 hours, 1000% for 2 cycles minimum.

Overcurrent Protection: External overcurrent protection provided by the supply branch cir- cuit breakers.

Short circuit withstand capability: up to 20,000 symmetrical amps, protected by internal fus- ing.

Withstands Transient Voltage Surges up to 6 kV as defined by IEEE C62.41 for Category A3.

Meets FCC Part 15 Class A Emission Limits.

ETL Listed under UL Standard 1008.

50 Hz units are CE marked for compliance with the EMC and Low Voltage Directives.

Redundant Control Power Supplies.

Integral Maintenance Bypass.

Eight Isolated Normally Open, Form A Switch Status Contacts.

RS-232 Communications Port

Hot-Swap, Plug-In Electronics Module.

1.1.3Environmental Specifications

Storage temperature range: -40° to +60°C

Operating temperature range: 0° to 40°C.

Relative Humidity: 0 to 95% without condensation

Operating Altitude: up to 5000 feet (1500 meters) above sea level without derating.

Storage/Transport Altitude: up to 40,000 feet (12,000 meters) above sea level.

Audible Noise: less than 45 dBA at 5 feet (1.5 meters).

Introduction 3

Image 7
Contents Power Protection SmartSwitchPage Table of Contents Figures Important Safety Instructions Introduction SpecificationsElectrical Specifications Enclosure SmartSwitch RatingsConnector Receptacle Voltage No. of Conductors Designation Phase Neutral Gnd Poles Amps Type Refer toLocation Considerations Unpacking and InstallationWire Size Tightening Torque Input and Output Power ConnectionsLb.-in N-m 17.25 18.5 469 Typical 25 to 60 Amp SmartSwitch Underfloor / Wallmount Unit Typical Input and Output Power Connections Grounding Control Wiring ConnectionsIndicator Description Description of SmartSwitch OperationStatus Indicators SmartSwitch Status IndicatorsRS-232 Communications Port RS-232 Ascii Communication Port Customer CommandsExample View Status Response Example View Event Log Response Example View Settings ResponseLogged Events include Operator Controls Bypass/Transfer Control SwitchOperating Guidelines Operating Guidelines Maintenance Maintenance Technical Support Automatic Transfer Switch