Liebert FS-8704-02 instruction manual Map Descriptor Example

Page 14

FS-8704-02_BacnetEthernet.doc Driver Manual

Page 14 of 20

5.4.3.Map Descriptor Example

//Server Side Map Descriptors

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

 

 

Data_Array_Name,

 

Data_Array_Offset,

Function,

Node_Name,

Object_Type,

Object_Instance

Property,

Units,

Relinquish_Default

 

SMD_AI_01,

 

 

DA_AI_01,

 

0,

Server,

Virtual_BCU_11,

AI,

1,

Present_Value,

Degrees-Fahrenheit,

-

 

SMD_AI_02,

 

 

DA_AI_01,

 

1,

Server,

Virtual_BCU_11,

AI,

2,

Present_Value,

Degrees-Fahrenheit,

-

 

SMD_AI_03,

 

 

DA_AI_01,

 

2,

Server,

Virtual_BCU_11,

AI,

3,

Present_Value,

Degrees-Fahrenheit,

-

 

SMD_AO_01,

 

 

DA_AO_01,

 

0,

Server,

Virtual_BCU_11,

AO,

1,

Present_Value,

percent-relative-humidity,

0

 

SMD_AO_02,

 

 

DA_AO_01,

 

1,

Server,

Virtual_BCU_11,

AO,

2,

Present_Value,

percent-relative-humidity,

0

 

SMD_AO_03,

 

 

DA_AO_01,

 

2,

Server,

Virtual_BCU_11,

AO,

3

Present_Value,

percent-relative-humidity,

0

//Server Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Object_Type,

Object_Instance,

Property

Relinquish_Default

SMD_DI_01,

DA_DI_01,

0,

Server,

Virtual_BCU_11,

DI,

1,

Present_Value

-

SMD_DI_02,

DA_DI_01,

1,

Server,

Virtual_BCU_11,

DI,

2,

Present_Value

-

SMD_DI_03,

DA_DI_01,

2,

Server,

Virtual_BCU_11,

DI,

3,

Present_Value

-

SMD_DO_01,

DA_DO_01,

0,

Server,

Virtual_BCU_11,

DO,

1,

Present_Value

0

SMD_DO_02,

DA_DO_01,

1,

Server,

Virtual_BCU_11,

DO,

2,

Present_Value

0

SMD_DO_03,

DA_DO_01,

2,

Server,

Virtual_BCU_11,

DO,

3,

Present_Value

0

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 14
Contents FS-8704-02 BACnet Ethernet Table of Contents BACnet Ethernet Description Provided by the Supplier of 3rd Party Equipment Hardware Hardware Connections Client Side Connection Descriptions Configuring the FieldServer as a BACnet Ethernet ClientData Arrays Client Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersMap Descriptor Examples Configuring the FieldServer as a BACnet Ethernet Server Server Side Connection DescriptorsServer Side Node Descriptors Driver Specific Map Descriptor Parameters Not foundObject Map Descriptor Example Appendix A. Advanced Topics Appendix A.1. BACnet Object NamesAppendix B. Troubleshooting Appendix B.1. Debugging a BACnet connection Hints and tipsAppendix C. Units Unit VariationKVA GPM This page Intentionally Left Blank