Liebert FS-8704-02 instruction manual Client Side Node Descriptors

Page 7

FS-8704-02_BacnetEthernet.doc Driver Manual

Page 7 of 20

Example

//Client Side Connections

Connections

 

 

Adapter,

Protocol,

Poll_Delay

N1,

Bacnet_Eth,

0.500s

4.3.Client Side Node Descriptors

Section Title

 

 

Nodes

 

 

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric

characters

 

 

Node_ID

BACnet station address of physical

1-16777215

Server node

 

 

Protocol

Specify protocol used

Bacnet_Eth

Adapter

Specify port Adapter used

N1

Example

//Client Side Nodes

Nodes

 

 

 

Node_Name,

Node_ID,

Protocol,

Adapter

BCU_01,

1,

Bacnet_Eth,

N1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 7
Contents FS-8704-02 BACnet Ethernet Table of Contents BACnet Ethernet Description Provided by the Supplier of 3rd Party Equipment Hardware Hardware Connections Data Arrays Configuring the FieldServer as a BACnet Ethernet ClientClient Side Connection Descriptions Client Side Node Descriptors Timing Parameters Driver Related Map Descriptor ParametersMap Descriptor Examples Server Side Connection Descriptors Configuring the FieldServer as a BACnet Ethernet ServerServer Side Node Descriptors Not found Driver Specific Map Descriptor ParametersObject Map Descriptor Example Appendix A.1. BACnet Object Names Appendix A. Advanced TopicsAppendix B.1. Debugging a BACnet connection Hints and tips Appendix B. TroubleshootingUnit Variation Appendix C. UnitsKVA GPM This page Intentionally Left Blank