Liebert FS-8704-02 instruction manual Appendix B. Troubleshooting

Page 16

FS-8704-02_BacnetEthernet.doc Driver Manual

Page 16 of 20

Appendix B. Troubleshooting

Appendix B.1. Debugging a BACnet connection: Hints and tips

Disconnect the FieldServer from the BACnet network when transferring BCU images to the BCU.

Should duplicate object instances be accidentally configured in the FieldServer, the second call of the instance will overwrite the first one. This may result in a BACnet Object being “lost.”

If “Virtual_BCU_…” is not being indicated as the device description for the FieldServer on the BACnet SCADA system, then the FieldServer is not communicating to the SCADA system. If the present value’s name is being indicated, but the present value shows question marks, then it is most likely that the Client side of the FieldServer is not communicating.

If new points are added to the FieldServer it is important to restart the Summit Workstation or BCU, otherwise these new points might not be seen by the FieldServer.

Poll only the BACnet addresses that exist in the device when communicating with Liebert systems. Polling addresses that are not configured in these systems will cause the connection to fail. The newer versions of Lieberts do not suffer from this problem. Please contact your Lieberts supplier for more information.

Extra memory is required to store Map Descriptors that have the active/inactive text parameters specified. If the defaults are appropriate, do not specify these parameters. This will save memory and allow more Map Descriptors to be created

Appendix B.2. BACnet Specific Statistics

Stat

Description

Resolution

 

 

It is normal to receive a few link control

 

A “who-is” link control message

messages. If the number is higher than the

Link Control

transmit/receive messages, however, there

was sent or received.

 

may be a problem with lost

 

 

 

 

communications..

Unsupported

A request for an unsupported

This is not an error. BACnet clients often

poll all properties of a particular object to

Properties

property was received.

determine which properties are supported.

 

 

 

Data was requested but the

 

Segmentation

response would have exceeded the

This is not an error - the BACnet client will

maximum size of the APDU and

use a different method to read data from

Not Supported

could not be sent using an un-

the FieldServer.

 

 

segmented message.

 

Sequence Error

Invoke ID of a reply did not match

You should not see this message. It

the Invoke ID of the poll.

normally indicates a configuration error.

 

 

 

This typically happens when trying to write

Write Access

A write to an object was denied.

to an Input Object that is not Out-Of-

Denied

Service. It is not possible to write to Input

 

 

 

Objects.

Exception

A BACnet Service was denied

This may be a problem on the Client

system. Consult the PIC statement to

Errors

because it is not supported

determine what services are supported.

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 16
Contents FS-8704-02 BACnet Ethernet Table of Contents BACnet Ethernet Description Provided by the Supplier of 3rd Party Equipment Hardware Hardware Connections Data Arrays Configuring the FieldServer as a BACnet Ethernet ClientClient Side Connection Descriptions Client Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersMap Descriptor Examples Configuring the FieldServer as a BACnet Ethernet Server Server Side Connection DescriptorsServer Side Node Descriptors Driver Specific Map Descriptor Parameters Not foundObject Map Descriptor Example Appendix A. Advanced Topics Appendix A.1. BACnet Object NamesAppendix B. Troubleshooting Appendix B.1. Debugging a BACnet connection Hints and tipsAppendix C. Units Unit VariationKVA GPM This page Intentionally Left Blank