5.Configuring the FieldServer as a BACnet Ethernet Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver CD).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a BACnet Ethernet Client
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet Ethernet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
5.1.Data Arrays
Section Title |
|
|
Data_Arrays |
|
|
Column Title | Function | Legal Values |
Data_Array_Name | Provide name for Data Array | Up to 15 alphanumeric characters |
Data_Format | Provides data format | FLOAT, BIT |
Data_Array_Length | Number of Data Objects | |
Example |
|
|
|
|
|
// Data Arrays |
|
|
Data_Arrays |
|
|
Data_Array_Name, | Data_Format, | Data_Array_Length |
DA_AI_01, | Float, | 200 |
DA_AO_01, | Float, | 200 |
DA_DI_01, | Bit, | 200 |
DA_DO_01, | Bit, | 200 |
5.2.Server Side Connection Descriptors
Section Title |
|
|
Connections |
|
|
Column Title | Function | Legal Values |
Adapter | Adapter Name | N1 |
Protocol | Specify protocol used | Bacnet_Eth |
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408)