Liebert FS-8704-02 Configuring the FieldServer as a BACnet Ethernet Client, Data Arrays

Page 6

FS-8704-02_BacnetEthernet.doc Driver Manual

Page 6 of 20

4.Configuring the FieldServer as a BACnet Ethernet Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a BACnet Ethernet Server.

4.1.Data Arrays

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

 

Section Title

 

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

 

Column Title

 

Function

 

 

Legal Values

 

 

Data_Array_Name

Provide name for Data Array

 

 

Up to 15 alphanumeric

 

 

 

characters

 

 

 

 

 

 

 

Data_Array_Format

 

Provide data format. Each Data Array

 

FLOAT, BIT

 

 

can only take on one format.

 

 

 

 

 

 

 

 

 

 

 

 

Number of Data Objects. Must be

 

 

 

 

 

Data_Array_Length

 

larger than the data storage area

 

 

1-10,000

 

 

 

required by the Map Descriptors for

 

 

 

 

 

 

 

 

 

 

 

 

 

the data being placed in this array.

 

 

 

 

 

 

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

 

Data_Array_Name,

 

Data_Format,

Data_Array_Length

 

 

DA_AI_01,

 

Float,

200

 

 

 

DA_AO_01,

 

Float,

200

 

 

 

DA_DI_01,

 

Bit,

200

 

 

 

DA_DO_01,

 

Bit,

200

 

 

4.2.Client Side Connection Descriptions

Section Title

 

 

 

Adapter

 

 

 

Column Title

Function

Legal Values

 

Adapter

Adapter Name

N1, N21

 

Protocol

Specify protocol used

Bacnet_Eth

 

Poll Delay*

Time between internal polls

0-32000s; 0.500s

 

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 6
Contents FS-8704-02 BACnet Ethernet Table of Contents BACnet Ethernet Description Provided by the Supplier of 3rd Party Equipment Hardware Hardware Connections Configuring the FieldServer as a BACnet Ethernet Client Data ArraysClient Side Connection Descriptions Client Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersMap Descriptor Examples Configuring the FieldServer as a BACnet Ethernet Server Server Side Connection DescriptorsServer Side Node Descriptors Driver Specific Map Descriptor Parameters Not foundObject Map Descriptor Example Appendix A. Advanced Topics Appendix A.1. BACnet Object NamesAppendix B. Troubleshooting Appendix B.1. Debugging a BACnet connection Hints and tipsAppendix C. Units Unit VariationKVA GPM This page Intentionally Left Blank