Liebert ITR Fan Speed Control Systems, Materials Supplied, Condenser refrigerant per serial tag

Page 23

 

 

 

 

 

 

 

 

 

Air-Cooled Models

 

Table 5

Equivalent lengths (feet) for various pipe fittings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copper Pipe

90 Degree

90 Degree

45 Degree

 

Gate

Globe

Angle

 

 

O.D. in.

 

Elbow Copper

Elbow Cast

Elbow

Tee

Valve

Valve

Valve

 

1/2

 

0.8

1.3

0.4

2.5

0.26

7.0

4.0

 

 

5/8

 

0.9

1.4

0.5

2.5

0.28

9.5

5.0

 

 

3/4

 

1.0

1.5

0.6

2.5

0.3

12.0

6.5

 

 

7/8

 

1.45

1.8

0.8

3.6

0.36

17.2

9.5

 

 

1-1/8

 

1.85

2.2

1.0

4.6

0.48

22.5

12.0

 

 

1-3/8

 

2.4

2.9

1.3

6.4

0.65

32.0

16.0

 

 

1-5/8

 

2.9

3.5

1.6

7.2

0.72

36.0

19.5

 

Refrigerant trap = 4 times equivalent length of pipe per this table.

Table 6

Indoor unit refrigerant charge lb (kg) R22 or R407C (per unit serial tag)

 

 

R22

R407C

 

 

 

 

 

 

 

 

Approximate Charge

Approximate Charge

 

Model

 

lb (kg)

lb (kg)

 

67A/65A

 

1.5 (0.68)

1.4 (0.6)

 

 

 

 

 

 

Table 7

Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube

 

 

 

R22

R407C

 

 

 

 

 

 

 

 

 

 

 

Liquid Line

 

Hot Gas Line

Liquid Line

Hot Gas Line

 

O.D.

 

lb (kg)

 

lbs (kg)

lb (kg)

lb (kg)

 

1/2"

 

7.3 (3.3)

 

1.3 (0.6)

6.9 (2.9)

-

 

5/8"

 

11.7 (5.3)

 

2.1 (1.0)

11.0 (4.6)

2.2 (0.9)

 

3/4"

 

16.6 (7.5)

 

3.0 (1.4)

15.7 (6.5)

3.1 (1.3)

 

7/8"

 

24.4 (11.1)

 

4.4 (2.0)

23.0 (9.6)

4.5 (1.9)

 

Table 8

Condenser refrigerant (per serial tag)

 

 

 

 

 

 

 

 

 

R22

R407C

 

 

 

 

Approximate Charge

Approximate Charge

 

lb (kg)

lb (kg)

Model

 

 

 

 

 

Fan Speed

 

Lee-Temp*

Fan Speed

Lee-Temp*

 

 

 

 

 

 

083

5 (2.27)

 

27 (12.3)

8 (3)

25 (12)

104

8 (3.63)

 

39 (17.7)

9 (4)

37 (17)

*Charge includes the receiver charge.

3.4Fan Speed Control Systems

Fan Speed Control provides an infinite number of speed variations on specially designed, permanent split-capacitor motors. The control module varies the air quantity passing over the condenser coil by monitoring refrigerant pressure.

3.4.1Materials Supplied

1.Built-in pre-wired condenser control box

2.Air-cooled condenser

3.Piping access cover to be reinstalled when piping is complete

4.Bolts (four per leg) 3/8" x 5/8"

5.Terminal block for two-wire, 24-volt interlock connection between unit and condenser

6.Condenser legs, four on one-fan models

17

Image 23
Contents Liebert Challenger ITR Page Table of Contents R407C Refrigerant Chilled Water ModelsSplit System Models Figures Tables System Descriptions Location Considerations Remote Sensor Installation LocationRoom Preparation Equipment InspectionDomestic Export Model Lb kg 50Hz Models 60Hz Models Unit shipping weightsHandling With Skid Removal of SkidUnit Weight Cabinet dimensionsSL-11897 Piping connection size Piping ConsiderationsDrain Line Piping Outlet Locations Piping connections for split system fan coil units Piping connections for water/glycol and Glycool units Piping connections for chilled water self-contained units Electrical connections Electrical ConnectionsDucted Applications Plenum InstallationBalancing the Air Distribution Checklist for Completed Installation Lee-Temp/Flood Back Head Pressure Control Condensers Condenser LocationLine Voltage Low VoltageAir-cooled condenser statistics Equivalent Length Hot Gas Line Liquid Line Refrigerant PipingRecommended line sizes OD copper inches 23 & 33 kW 067A 065ACondenser refrigerant per serial tag Fan Speed Control SystemsMaterials Supplied Equivalent lengths feet for various pipe fittingsDehydration/Leak Test Single Circuit Shown Piping Refrigerant control settings psi kPaLee-Temp/Flood Back Head Pressure Control Systems ChargingMaterials Supplied Low Pressure Cut Out High Pressure Cut Out 360 Single Circuit Shown Condenser Water-cooled general arrangement Water Regulating Valve Manual Flushing Water Regulating Valve AdjustmentTesting Valve Function Water Regulating ValvePump and Drycooler Drycooler InstallationDrycooler Location Dry Bulb Wet Bulb Relative Dew Point Humidity Room dew point temperaturesGlycol Piping Expansion Tanks, Fluid Relief Valves and Other DevicesPreparing the System for Filling Indoor unit glycol volume approximate gallons liters maxVolume in standard Type L copper piping Filling Instructions@ 50F 10C Glycol SolutionsEthylene glycol concentrations Filling the System 483mm 43-3/16 1097mm For expansion tank dimensions, see on43-9/16 110 5mm See Note 30-1/4Pump Pump Suction Pump Discharge Connection Mounting hole dimensional dataDrycooler data Glycol pump dataGlycol general arrangement Glycool general arrangement Glycol Regulating Valve Glycol Regulating Valve AdjustmentChilled Water Models Water/Glycol-Cooled Condensing Units Air-Cooled Condensing UnitsRefrigerant Loop Line coupling sizes Unit refrigerant chargeRecommended refrigerant lines R22 or R407C sizes OD copper Evaporator Condensing Unit EvaporatorQuick Connect Fittings Outdoor Air-Cooled Condensing Units Unit Dimensions See TablePFH067A-L See Table Outdoor air-cooled condensing unit-top air discharge models152 Piping and electrical connections top air discharge36-1/4 38-1/2 SL-11081 PG 8A Electrical field connections, prop fan condensing moduleIndoor centrifugal condensing unit Installing the Indoor Condensing UnitModel Net Weight 60 Hz 50 Hz Lb kg MC65A MC64A Centrifugal Air-Cooled Condensing UnitsAirflow CFM CMH DuctingCentrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Condenser Water Requirements Regulating Valve Adjustment and TestingWater and Glycol-Cooled Condensing Units Piping ConsiderationsWater/glycol-cooled condensing unit dimensions WATER/GLYCOL R407C Refrigerant Temperature Gauge Pressure Psig KPaExample Temperature Pressure Gauge Psig KPaCalculating Subcooling That Ne tIti Ti n

ITR specifications

The Liebert ITR is an advanced precision cooling unit designed to maintain optimal temperature and humidity levels in mission-critical environments. Engineered for high-performance applications, it is particularly suitable for data centers, telecommunications facilities, and other spaces that require precise climate control to ensure uninterrupted operation of sensitive equipment.

One of the main features of the Liebert ITR is its modular design. This allows for scalability and flexibility, enabling users to customize the system based on their specific cooling needs. The unit can be configured in various sizes and cooling capacities, making it suitable for both small server rooms and large data centers. This adaptability is crucial for organizations that anticipate growth and require an efficient cooling solution that can evolve with their infrastructure.

The Liebert ITR incorporates state-of-the-art technologies to enhance performance and energy efficiency. Among these technologies is the use of a variable speed compressor that adjusts its speed based on the cooling load. This capability not only improves energy efficiency but also significantly reduces operational costs by minimizing electricity consumption when cooling demands fluctuate.

Additionally, the unit features advanced control systems that provide intelligent monitoring and management of temperature and humidity levels. These systems can integrate seamlessly with building management systems (BMS) and can be operated remotely, providing users with real-time insights into the performance of the cooling system. Such connectivity ensures quick identification and resolution of potential issues, thereby reducing downtime and maintaining optimal conditions for critical equipment.

The Liebert ITR utilizes eco-friendly refrigerants, contributing to reduced environmental impact while ensuring compliance with regulatory standards. The unit's design also emphasizes reliability, featuring robust construction and redundant components that enhance longevity and minimize the likelihood of failures.

Furthermore, the Liebert ITR is equipped with advanced filtration systems that maintain air quality by reducing particulate matter and contaminants, ensuring that the atmosphere within data centers is not only cool but also clean—critical for the longevity of sensitive electronic equipment.

Overall, the Liebert ITR is characterized by its innovative design, energy-efficient operation, and comprehensive control capabilities, making it an ideal choice for businesses looking to safeguard their critical infrastructure from overheating and humidity. As climate control becomes increasingly important in the digital age, the Liebert ITR stands out as a reliable solution for maintaining optimal environmental conditions.