Liebert ITR installation manual Ducting, Airflow CFM CMH

Page 55

Split System Models

Figure 23 Detail of ceiling hanging bracket

3/8" threaded rod (field-supplied)

3/8" hex nut

3/8" washer

Sleeve

Isolator

3/8" fender washer

3/8" hex nut

3/8" hex nut Nylock

Unit base pan (ref)

7.5.2Ducting

The total external static pressure for the inlet and outlet ducts, including grille, must not exceed 0.5 inches of H2O. Hood intake dimensions should be the same as the condensing unit duct dimen- sions.

If the condensing unit is located close to the outside of the building, rain hoods must be installed. In addition, install a triple layer bird screen over rain hood openings to eliminate the possibility of insects, birds, water, or debris entering the unit.

Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and to control vibration transmission to the building. Attach the ductwork to the unit using the flanges provided. Locate the unit and ductwork so that the return air does not short circuit to the supply air inlet.

Avoid directing the hot exhaust air toward adjacent doors or windows.

Normal operating sound may be objectionable if the condensing unit is placed directly over quiet work areas. Ductwork that runs through a conditioned space or is exposed to areas where condensation may occur must be insulated. Whenever possible, ductwork should be suspended using flexible hang- ers. Ductwork should not be fastened directly to the building structure. In applications where the ceil- ing plenum is used as the heat rejection domain, the discharge air must be directed away from the condensing unit air inlet and a screen must be added to the end of the discharge duct to protect ser- vice personnel.

For multiple unit installations, space the units so that the hot condensing unit exhaust air is not directed toward the air inlet of an adjacent unit.

Table 29 Airflow CFM (CMH)

 

23 & 33 kW

 

 

60 Hz

3500 (5947)

 

 

50 Hz

3500 (5947)

 

 

49

Image 55
Contents Liebert Challenger ITR Page Table of Contents Split System Models Chilled Water ModelsR407C Refrigerant Figures Tables System Descriptions Location Considerations Remote Sensor Installation LocationRoom Preparation Equipment InspectionDomestic Export Model Lb kg 50Hz Models 60Hz Models Unit shipping weightsHandling With Skid Removal of SkidUnit Weight Cabinet dimensionsSL-11897 Drain Line Piping ConsiderationsPiping connection size Piping Outlet Locations Piping connections for split system fan coil units Piping connections for water/glycol and Glycool units Piping connections for chilled water self-contained units Electrical connections Electrical ConnectionsBalancing the Air Distribution Plenum InstallationDucted Applications Checklist for Completed Installation Lee-Temp/Flood Back Head Pressure Control Condensers Condenser LocationLine Voltage Low VoltageAir-cooled condenser statistics Equivalent Length Hot Gas Line Liquid Line Refrigerant PipingRecommended line sizes OD copper inches 23 & 33 kW 067A 065ACondenser refrigerant per serial tag Fan Speed Control SystemsMaterials Supplied Equivalent lengths feet for various pipe fittingsDehydration/Leak Test Single Circuit Shown Piping Refrigerant control settings psi kPaLee-Temp/Flood Back Head Pressure Control Systems ChargingMaterials Supplied Low Pressure Cut Out High Pressure Cut Out 360 Single Circuit Shown Condenser Water-cooled general arrangement Water Regulating Valve Manual Flushing Water Regulating Valve AdjustmentTesting Valve Function Water Regulating ValveDrycooler Location Drycooler InstallationPump and Drycooler Dry Bulb Wet Bulb Relative Dew Point Humidity Room dew point temperaturesGlycol Piping Expansion Tanks, Fluid Relief Valves and Other DevicesPreparing the System for Filling Indoor unit glycol volume approximate gallons liters maxVolume in standard Type L copper piping Filling InstructionsEthylene glycol concentrations Glycol Solutions@ 50F 10C Filling the System 483mm 43-3/16 1097mm For expansion tank dimensions, see on43-9/16 110 5mm See Note 30-1/4Pump Pump Suction Pump Discharge Connection Mounting hole dimensional dataDrycooler data Glycol pump dataGlycol general arrangement Glycool general arrangement Glycol Regulating Valve Glycol Regulating Valve AdjustmentChilled Water Models Water/Glycol-Cooled Condensing Units Air-Cooled Condensing UnitsRefrigerant Loop Recommended refrigerant lines R22 or R407C sizes OD copper Unit refrigerant chargeLine coupling sizes Evaporator Condensing Unit EvaporatorQuick Connect Fittings Outdoor Air-Cooled Condensing Units Unit Dimensions See TablePFH067A-L See Table Outdoor air-cooled condensing unit-top air discharge models36-1/4 38-1/2 Piping and electrical connections top air discharge152 SL-11081 PG 8A Electrical field connections, prop fan condensing moduleIndoor centrifugal condensing unit Installing the Indoor Condensing UnitModel Net Weight 60 Hz 50 Hz Lb kg MC65A MC64A Centrifugal Air-Cooled Condensing UnitsAirflow CFM CMH DuctingCentrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Condenser Water Requirements Regulating Valve Adjustment and TestingWater and Glycol-Cooled Condensing Units Piping ConsiderationsWater/glycol-cooled condensing unit dimensions WATER/GLYCOL R407C Refrigerant Temperature Gauge Pressure Psig KPaCalculating Subcooling Temperature Pressure Gauge Psig KPaExample That Ne tIti Ti n

ITR specifications

The Liebert ITR is an advanced precision cooling unit designed to maintain optimal temperature and humidity levels in mission-critical environments. Engineered for high-performance applications, it is particularly suitable for data centers, telecommunications facilities, and other spaces that require precise climate control to ensure uninterrupted operation of sensitive equipment.

One of the main features of the Liebert ITR is its modular design. This allows for scalability and flexibility, enabling users to customize the system based on their specific cooling needs. The unit can be configured in various sizes and cooling capacities, making it suitable for both small server rooms and large data centers. This adaptability is crucial for organizations that anticipate growth and require an efficient cooling solution that can evolve with their infrastructure.

The Liebert ITR incorporates state-of-the-art technologies to enhance performance and energy efficiency. Among these technologies is the use of a variable speed compressor that adjusts its speed based on the cooling load. This capability not only improves energy efficiency but also significantly reduces operational costs by minimizing electricity consumption when cooling demands fluctuate.

Additionally, the unit features advanced control systems that provide intelligent monitoring and management of temperature and humidity levels. These systems can integrate seamlessly with building management systems (BMS) and can be operated remotely, providing users with real-time insights into the performance of the cooling system. Such connectivity ensures quick identification and resolution of potential issues, thereby reducing downtime and maintaining optimal conditions for critical equipment.

The Liebert ITR utilizes eco-friendly refrigerants, contributing to reduced environmental impact while ensuring compliance with regulatory standards. The unit's design also emphasizes reliability, featuring robust construction and redundant components that enhance longevity and minimize the likelihood of failures.

Furthermore, the Liebert ITR is equipped with advanced filtration systems that maintain air quality by reducing particulate matter and contaminants, ensuring that the atmosphere within data centers is not only cool but also clean—critical for the longevity of sensitive electronic equipment.

Overall, the Liebert ITR is characterized by its innovative design, energy-efficient operation, and comprehensive control capabilities, making it an ideal choice for businesses looking to safeguard their critical infrastructure from overheating and humidity. As climate control becomes increasingly important in the digital age, the Liebert ITR stands out as a reliable solution for maintaining optimal environmental conditions.