Liebert ITR Room Preparation, Equipment Inspection, Location Considerations, Equipment Handling

Page 8

Installation

2.0INSTALLATION

2.1Room Preparation

The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling can be a polyethylene film type. Use a rubber or plastic base paint on concrete walls and floors. Doors should not be undercut or have grilles in them.

Outside (or fresh) air should be kept to an absolute minimum. Outside air adds to the heating, cool- ing, humidifying and dehumidifying loads of the site. It is recommended that outside air be kept below 5% of the total air circulated in the room and be preconditioned.

2.2Equipment Inspection

Upon arrival of the unit, inspect all items for visible and concealed damage. Damage should be imme- diately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative.

2.3Location Considerations

The Liebert Challenger ITR can sit on top of an accessible elevated flooring system. It may be neces- sary to furnish additional pedestal support below the unit to ensure maximum structural support (see Table 1). A separate floor stand for the unit may be used as support, independent of the elevated floor and installed prior to the flooring system.

Provide approximately 34" (864 mm) service clearance in the front and rear of the unit.

The unit can be installed between equipment racks or at the end of a row of racks. Consideration should be given before installing refrigerant and liquid lines next to, under or above electronic equip- ment. Avoid placing the Liebert Challenger ITR in an alcove. Placing units too close together will reduce the effectiveness of the air distribution.

NOTE

Locate and remove shipping screw on fan motor base.

2.3.1Remote Sensor Installation Location

The remote temperature and humidity sensor should be installed in the cold aisle in front of the equipment to be cooled. It should be mounted at the farthest point from the cooling unit that supply air needs to reach but still within the unit's area of influence. The sensor should be installed at the highest point that equipment will draw in cooled air.

2.4Equipment Handling

! WARNING

Risk of equipment tipping over. Can cause damage, injury or death.

The instructions listed below must be adhered to when handling this unit with or without the skid. There is the potential for this unit to tip over if handled improperly.

2

Image 8 Contents
Liebert Challenger ITR Page Table of Contents R407C Refrigerant Chilled Water Models Split System Models Figures Tables System Descriptions Remote Sensor Installation Location Room PreparationEquipment Inspection Location ConsiderationsUnit shipping weights Handling With SkidRemoval of Skid Domestic Export Model Lb kg 50Hz Models 60Hz ModelsCabinet dimensions Unit WeightSL-11897 Piping connection size Piping ConsiderationsDrain Line Piping Outlet Locations Piping connections for split system fan coil units Piping connections for water/glycol and Glycool units Piping connections for chilled water self-contained units Electrical Connections Electrical connectionsDucted Applications Plenum InstallationBalancing the Air Distribution Checklist for Completed Installation Condenser Location Line VoltageLow Voltage Lee-Temp/Flood Back Head Pressure Control CondensersAir-cooled condenser statistics Refrigerant Piping Recommended line sizes OD copper inches23 & 33 kW 067A 065A Equivalent Length Hot Gas Line Liquid LineFan Speed Control Systems Materials SuppliedEquivalent lengths feet for various pipe fittings Condenser refrigerant per serial tagDehydration/Leak Test Single Circuit Shown Refrigerant control settings psi kPa Lee-Temp/Flood Back Head Pressure Control SystemsCharging PipingMaterials Supplied Low Pressure Cut Out High Pressure Cut Out 360 Single Circuit Shown Condenser Water-cooled general arrangement Water Regulating Valve Adjustment Testing Valve FunctionWater Regulating Valve Water Regulating Valve Manual FlushingPump and Drycooler Drycooler InstallationDrycooler Location Room dew point temperatures Glycol PipingExpansion Tanks, Fluid Relief Valves and Other Devices Dry Bulb Wet Bulb Relative Dew Point HumidityIndoor unit glycol volume approximate gallons liters max Volume in standard Type L copper pipingFilling Instructions Preparing the System for Filling@ 50F 10C Glycol SolutionsEthylene glycol concentrations Filling the System For expansion tank dimensions, see on 43-9/16 110 5mmSee Note 30-1/4 483mm 43-3/16 1097mmMounting hole dimensional data Drycooler dataGlycol pump data Pump Pump Suction Pump Discharge ConnectionGlycol general arrangement Glycool general arrangement Glycol Regulating Valve Adjustment Glycol Regulating ValveChilled Water Models Air-Cooled Condensing Units Water/Glycol-Cooled Condensing UnitsRefrigerant Loop Line coupling sizes Unit refrigerant chargeRecommended refrigerant lines R22 or R407C sizes OD copper Evaporator Evaporator Condensing UnitQuick Connect Fittings Unit Dimensions See Table Outdoor Air-Cooled Condensing UnitsPFH067A-L Outdoor air-cooled condensing unit-top air discharge models See Table152 Piping and electrical connections top air discharge36-1/4 38-1/2 Electrical field connections, prop fan condensing module SL-11081 PG 8AInstalling the Indoor Condensing Unit Model Net Weight 60 Hz 50 Hz Lb kg MC65A MC64ACentrifugal Air-Cooled Condensing Units Indoor centrifugal condensing unitDucting Airflow CFM CMHCentrifugal air-cooled condensing unit dimensional data AIR Cooled Water Cooled Regulating Valve Adjustment and Testing Water and Glycol-Cooled Condensing UnitsPiping Considerations Condenser Water RequirementsWater/glycol-cooled condensing unit dimensions WATER/GLYCOL Temperature Gauge Pressure Psig KPa R407C RefrigerantExample Temperature Pressure Gauge Psig KPaCalculating Subcooling Ne t ItiTi n That