Liebert 700-3000 VA user manual Battery Replacement Procedures, For 700/1000 VA MINI-TOWER Models

Page 16

BATTERY REPLACEMENT PROCEDURES

CAUTION – A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:

-Turn off and disconnect the UPS from the utility power prior to opening the battery replacement door.

-Remove rings, watches, and other metal objects.

-Use a Phillips (cross head) screwdriver with insulated grips.

-Do not lay tools or other metal objects on top of the batteries.

-If the battery replacement kit is damaged in any way or shows signs of leakage, contact your dealer immediately.

-Do not dispose of batteries in a fire, the batteries may explode.

-If you feel unqualified to replace the batteries, do not open the battery door. Call Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.

MINI-TOWER BATTERY REPLACEMENT

Battery door screws

Battery connector

FOR 700/1000 VA MINI-TOWER MODELS:

1.Gently lay the UPS on its right side.

2.Loosen and remove the five screws on the battery door. Remove the door by sliding it toward the rear of UPS and lifting it off. Lay the battery door aside for reassembly.

3.Gently pull battery wiring out and disconnect the battery connector.

4.Grasp the battery assembly, and pull it out of the UPS.

5.Unpack the new battery assembly taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same quantity and voltage rating (see specifications). If so, proceed with step 6; otherwise STOP and contact your dealer or LTS.

6.Slide the new battery assembly into the cavity, noting the connector is facing outward. Connect the battery connector together.

NOTE: There will be a small spark when connecting the battery connector. This is normal and will not harm you or the UPS.

16

DISCONTINUED

PRODUCT

Image 16
Contents UPStation GXT Important Safety Instructions Introduction and System Description RECTIFIER/POWER Factor Correction PFC Circuit Battery ChargerMajor Components InverterDC to DC Converter BatteryDynamic Bypass General Installation MINI-TOWER/TOWER UPS InstallationsRACK-MOUNT Conversion Diagrams RACK-MOUNT UPS Conversion and InstallationBattery Cabinet Installation Diagram Optional Battery Cabinets InstallationFerrite Bead Installation Serial CommunicationsUpstation GXT Controls and Indicators On/Alarm Silence/Manual Battery Test ButtonNormal Mode Operation Operation Battery Mode Operation Battery Recharge ModeUPS Monitoring Communications Interface PortPIN Assignmentcollector to Emiter UPS Intelligent Communications MaintenanceUPS Intellislot Communications Battery Replacement Procedures For 700/1000 VA MINI-TOWER ModelsFor 1000 to 3000 VA RACK/TOWER Models Tower Models only RACK/TOWER ModelsRack / Tower Battery Replacement Upstation GXT Battery RUN Times Internal Battery minutesFuse Replacement Procedures Audible Alarm ConditionsTroubleshooting Troubleshooting Guide Problem Cause SolutionSpecifications VA/WGXT1000RT-120 GXT1000RTE-120 Weight kg lbs Battery Cabinet Specifications Used w/ UPS ModelLimited Warranty 700-3000 VA 120