Liebert 700-3000 VA Battery Cabinet Installation Diagram, Optional Battery Cabinets Installation

Page 8

12.Plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with the National And Local Codes. Use a 15 amp rated device for the 1000, or 1500 VA units, a 20 amp device for the 2000 VA unit, and a 30 amp device for the 3000 VA unit. The wall receptacle must be grounded.

13.Locate UPS indoors in a controlled environment, where it cannot be accidentally turned off. Locate it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, or conductive contaminants. Maintain a minimum of 4 inches (100 mm) clearance in front and rear of the UPS. Maintain an ambient temperature range of 32° to 104° F (0° to 40° C).

NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery life.

14.Turn on the UPS by pressing the On button; then turn on the connected load equipment. The UPS is ready for normal operation.

OPTIONAL BATTERY CABINET(S) INSTALLATION

Up to two optional battery cabinets may be connected to the UPS to provide additional run time. Battery cabinets are designed to be placed on either side or beneath the UPS.

1.Unpack the UPS battery cabinet(s) carefully noting the packing method. Retain the box and packing material for possible future shipment.

2.CAUTION: The battery cabinet(s) are heavy (see specifications). Take proper precautions when lifting or moving them.

3.Visually inspect the UPS for freight damage. Report damage to the carrier and your dealer.

4.Follow the same installation instructions used earlier for the UPS (tower or rack-mount).

5.Attach external battery cabinets as shown, using the enclosed metal securing plate to prevent tip-over.

6.Connect the supplied cable to the battery cabinet then to the UPS.

7.Turn on the breaker on the rear of the battery cabinet.

Battery Cabinet Installation Diagram

SECURING PLATE

BREAKER

DISCONTINUED

PRODUCT

Image 8
Contents UPStation GXT Important Safety Instructions Introduction and System Description RECTIFIER/POWER Factor Correction PFC Circuit Battery ChargerMajor Components Inverter Dynamic Bypass Battery DC to DC Converter General Installation MINI-TOWER/TOWER UPS InstallationsRACK-MOUNT Conversion Diagrams RACK-MOUNT UPS Conversion and InstallationBattery Cabinet Installation Diagram Optional Battery Cabinets InstallationFerrite Bead Installation Serial CommunicationsUpstation GXT Controls and Indicators On/Alarm Silence/Manual Battery Test ButtonNormal Mode Operation OperationBattery Mode Operation Battery Recharge ModePIN Assignmentcollector to Emiter Communications Interface PortUPS Monitoring UPS Intellislot Communications MaintenanceUPS Intelligent Communications Battery Replacement Procedures For 700/1000 VA MINI-TOWER ModelsFor 1000 to 3000 VA RACK/TOWER Models Tower Models only RACK/TOWER ModelsRack / Tower Battery Replacement Upstation GXT Battery RUN Times Internal Battery minutesFuse Replacement Procedures Audible Alarm ConditionsTroubleshooting Troubleshooting Guide Problem Cause SolutionSpecifications VA/WGXT1000RT-120 GXT1000RTE-120 Weight kg lbs Battery Cabinet Specifications Used w/ UPS ModelLimited Warranty 700-3000 VA 120