BATTERY CABINET SPECIFICATIONS
MODEL NUMBER | GXT36VBATT |
| GXT48VBATT |
| GXT96VBATT |
Used w/ UPS Model | 1000RT |
| 1500RT |
| 2000RT/3000RT |
DIMENSIONS: in (mm) |
|
|
|
|
|
Unit | 177 x 522 x 430 |
| 177 x 522 x 430 |
| 177 x 522 x 430 |
W x D x H | (7.0 x 19.3 x 16. 9) |
| (7.0 x 19.3 x 16. 9) |
| (7.0 x 19.3 x 16. 9) |
Shipping | 13.38 x 26.0 x 22.25 |
| 13.38 x 26.0 x 22.25 |
| 13.38 x 26.0 x 22.25 |
W x D x H | (340 x 660 x 565) |
| (340 x 660 x 565) |
| (340 x 660 x 565) |
WEIGHT: lbs (kg) |
|
|
|
|
|
Unit | 61.3 (27.9) |
| 71.6 (32.5) |
| 71.6 (32.5) |
Shipping | 68.4 (31) |
| 78.7 (35.7) |
| 78.7 (35.7) |
BATTERY PARAMETERS |
|
|
|
|
|
Type | |||||
# of Strings x Qty/Str. x | 2x3x12Vx7.0 or 7.2 AH |
| 2x4x12Vx7.0 or 7.2 AH |
| 1x8x12Vx7.0 or 7.2 |
Batt. Voltage x Batt. |
|
| |||
|
|
|
| AH | |
Rating |
|
|
|
| |
|
|
|
|
| |
Batt. Mfg./ Part # | CSB GP1270F2 or Panasonic | ||||
See Typical Battery Discharge Curves | |||||
Recharge Time | 5 Hours to 95% capacity after full discharge into 100% load | ||||
ENVIROMENTAL |
|
|
|
|
|
Operating | +32° F to +104° F (0° C to +40° C) | ||||
Temperature |
|
|
|
|
|
Storage | +5° F to +122 °F | ||||
Temperature |
|
|
|
|
|
Relative Humidity |
| 0% to 95%, |
| ||
Operating Elevation | Up to 10,000 ft. (3000 m) at 40° C without derating | ||||
Storage Elevation | 50,000 ft. (15.000 m) maximum |
| |||
AGENCY |
|
|
|
|
|
Safety | UL 1778, | ||||
RFI/EMI | FCC Part 15, Subpart B, Class A; EN5022 Class B; CE ECM compliant | ||||
Immunity | IEEE 587 Category A; IEC | ||||
|
|
|
26
DISCONTINUED