TROUBLESHOOTING GUIDE
PROBLEM |
| CAUSE |
| SOLUTION |
|
|
|
| |||
UPS fails to start |
| UPS is short circuited or |
| Ensure UPS is off. Disconnect all loads |
|
when on button is |
| overloaded |
| and ensure nothing is lodged in output |
|
pressed |
|
|
| sockets. Ensure loads are not defective |
|
|
|
|
| or shorted internally. |
|
|
| Internal fuse is blown, |
| Do not attempt to open or service the |
|
|
| indicating internal fault |
| UPS. Contact your dealer or LTS. |
|
Battery indicator is |
| UPS not plugged in |
| UPS is operating from battery mode, |
|
illuminated |
|
|
| make certain UPS is securely plugged |
|
|
|
|
| into the wall socket |
|
|
| UPS input protection has |
| UPS is operating from battery mode. |
|
|
| opened |
| Save data and close applications. |
|
|
|
|
| Replace UPS input fuse or reset input |
|
|
|
|
| breaker, then restart UPS. |
|
|
| Utility voltage out of UPS |
| UPS is operating from battery mode. |
|
|
| input range. |
| Save data and close applications. |
|
|
|
|
| Ensure utility supply voltage is within |
|
|
|
|
| acceptable limits for UPS. |
|
UPS has reduced |
| Batteries not fully charged |
| Keep UPS plugged in continuously at |
|
battery time |
|
|
| least 24 hours to recharge batteries |
|
|
| UPS is overloaded |
| Check load level display and reduce load |
|
|
|
|
| level |
|
|
| Batteries may not be able to |
| Replace batteries. Contact your dealer |
|
|
| hold a full charge due to age |
| or LTS for replacement battery kit |
|
Fault and Bypass |
| UPS overloaded or load |
| Check load level display and remove |
|
indicators and all load |
| equipment is faulty |
|
| |
level LEDs are |
|
|
| VA and reduce number of loads |
|
illuminated |
|
|
| connected to UPS. Check load |
|
|
|
|
| equipment for faults. |
|
Fault and Bypass |
| UPS internal fan has a |
| Ensure UPS is not overloaded, |
|
indicators and |
| problem or UPS shutdown |
| ventilation openings not blocked, or room |
|
diagnostic LED A are |
| due to temperature condition. |
| ambient temperature not excessive. |
|
illuminated |
| Load is on bypass power |
| Wait 30 minutes to allow UPS to cool, |
|
|
|
|
| then restart UPS. IF it does not restart, |
|
|
|
|
| contact your dealer or LTS. |
|
Fault and Bypass |
| UPS internal DC bus |
| UPS requires service. Contact your |
|
indicators and |
| overvoltage |
| dealer or LTS. |
|
diagnostic LED B are |
|
|
|
|
|
illuminated |
|
|
|
|
|
Fault and Bypass |
| UPS power control fault. |
| UPS requires service. Contact your |
|
indicators and |
|
|
| dealer or LTS. |
|
diagnostic LED C are |
|
|
|
|
|
illuminated |
|
|
|
|
|
Fault and Bypass |
| UPS PFC fault. |
| UPS requires service. Contact your |
|
indicators and |
|
|
| dealer or LTS. |
|
diagnostic LED D are |
|
|
|
|
|
illuminated |
|
|
|
|
|
Fault and Bypass |
| UPS inverter fault. |
| UPS requires service. Contact your |
|
indicators and |
|
|
| dealer or LTS. |
|
diagnostic LED E are |
|
|
|
|
|
illuminated |
|
|
|
|
|
Fault and Bypass |
| UPS failed the battery test. |
| Replace batteries. Contact your dealer |
|
indicators and |
|
|
| or LTS. |
|
diagnostic LED A & C |
|
|
|
|
|
are illuminated |
|
|
|
|
|
Fault and Bypass |
| UPS shutdown due to a |
| Your UPS has received a signal or |
|
indicators and |
| command from the |
| command from the attached computer. If |
|
diagnostic LED C & E |
| communications port(s) |
| this was inadvertent, ensure the |
|
are illuminated |
|
|
| communication cable used is correct for |
|
|
|
|
| your system. For assistance, contact |
|
|
|
|
| your dealer or LTS. |
|
22