Liebert 700-3000 VA user manual GXT1000RT-120 GXT1000RTE-120

Page 24

SPECIFICATIONS

MODEL NUMBER

GXT1000RT-120

GXT1000RTE-120

MODEL RATING

1000 / 700

1000 / 700

VA/W

 

 

DIMENSIONS: in (mm)

 

 

Unit

7.0 x 19.3 x 16.9

7.0 x 19.3 x 16.9

W x D x H

(177 x 522 x 430)

(177 x 522 x 430)

Shipping

13.38 x 26.0 x 22.25

13.38 x 26.0 x 22.25

W x D x H

(340 x 660 x 565)

(340 x 660 x 565)

WEIGHT: lbs (kg)

 

 

Unit

51.9 (23.6)

68.4 (31.1)

Shipping

59.0 (26.8)

75.5 (34.3)

INPUT AC PARAMETERS

 

 

Voltage Range (typical)

120 VAC nominal; variable based upon output load

100% - 70% Loading

80-83 VAC to 134-138 VAC

70% - 30% Loading

70-73 VAC to 134-138 VAC

30% - 0% Loading

60-62 VAC to 134-138 VAC

Frequency

48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing

Input Power Cord

6 ft. detached,

6 ft. detached,

 

w/ NEMA 5-15 plug

w/ NEMA 5-15 plug

OUTPUT AC PARAMETERS

 

 

Output Receptacles

(8) NEMA 5-15R

(8) NEMA 5-15R

Voltage

100/110/120/127 (switch

selectable) VAC; ±3%

Frequency

50 Hz or 60Hz

Waveform

Sinewave

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

BATTERY PARAMETERS

 

 

Type

Valve-regulated, nonspillable, lead acid

Qty. x Voltage x Rating

3 x 12V x 7 or 7.2 AH

6 x 12V x 7 AH

Batt. Mfg./ Part #

CSB GP1270F2 or Panasonic LC-R127R2CH1

Back-up Time

See Typical Battery Discharge Curves

Recharge Time

5 Hours to 95% capacity after

10 Hours to 95% capacity after

 

full discharge into 100% load

full discharge into 100% load

ENVIROMENTAL

 

 

Operating Temperature

+32° F to +104° F (0° C to +40° C)

Storage Temperature

+5° F to +122 °F (-15° C to +50° C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to10,000 ft. (3000 m) at 40° C without derating

Storage Elevation

50,000 ft. (15,000 m) maximum

Audible Noise

<45 dBA, at 1 meter

AGENCY

 

 

Safety

UL 1778, c-UL Listed

RFI/EMI

FCC Part 15, Subpart B, Class A

Immunity

IEEE 587 Category A

24

DISCONTINUED

PRODUCT

Image 24
Contents UPStation GXT Important Safety Instructions Introduction and System Description RECTIFIER/POWER Factor Correction PFC Circuit Battery ChargerMajor Components InverterBattery DC to DC ConverterDynamic Bypass General Installation MINI-TOWER/TOWER UPS InstallationsRACK-MOUNT Conversion Diagrams RACK-MOUNT UPS Conversion and InstallationBattery Cabinet Installation Diagram Optional Battery Cabinets InstallationFerrite Bead Installation Serial CommunicationsUpstation GXT Controls and Indicators On/Alarm Silence/Manual Battery Test ButtonNormal Mode Operation OperationBattery Mode Operation Battery Recharge ModeCommunications Interface Port UPS MonitoringPIN Assignmentcollector to Emiter Maintenance UPS Intelligent CommunicationsUPS Intellislot Communications Battery Replacement Procedures For 700/1000 VA MINI-TOWER ModelsFor 1000 to 3000 VA RACK/TOWER Models Tower Models only RACK/TOWER ModelsRack / Tower Battery Replacement Upstation GXT Battery RUN Times Internal Battery minutesFuse Replacement Procedures Audible Alarm Conditions Troubleshooting Troubleshooting Guide Problem Cause SolutionSpecifications VA/WGXT1000RT-120 GXT1000RTE-120 Weight kg lbs Battery Cabinet Specifications Used w/ UPS ModelLimited Warranty 700-3000 VA 120