MODEL NUMBER

GXT700MT-120

 

GXT1000MT-120

MODEL RATING

700 / 490

 

1000 / 700

VA/W

 

 

 

DIMENSIONS: in (mm)

 

 

 

Unit

6.4 x 15.6 x 8.9

 

6.4 x 15.6 x 8.9

W x D x H

(162 x 430 x 225)

 

(162 x 430 x 225)

Shipping

11.0 x 19.75 x 14.25

 

11.0 x 19.75 x 14.25

W x D x H

(280 x 502 x 362)

 

(280 x 502 x 362)

WEIGHT: lbs (kg)

 

 

 

Unit

28.8 (13.1)

 

34.8 (15.8)

Shipping

33.0 (15.0)

 

39.0 (17.7)

INPUT AC PARAMETERS

 

 

 

Voltage Range (typical)

120 VAC nominal; variable based upon output load

100% - 70% Loading

80-83 VAC to 134-138 VAC

70% - 30% Loading

70-73 VAC to 134-138 VAC

30% - 0% Loading

60-62 VAC to 134-138 VAC

Frequency

48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing

Input Power Cord

6 ft. detached,

 

6 ft. detached,

 

w/ NEMA 5-15 plug

 

w/ NEMA 5-15 plug

OUTPUT AC PARAMETERS

 

 

 

Output Receptacles

(4) NEMA 5-15R

 

(4) NEMA 5-15R

Voltage

100/110/120/127 (switch

selectable) VAC; ±3%

Frequency

 

50 Hz or 60Hz

Waveform

 

Sinewave

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

BATTERY PARAMETERS

 

 

 

Type

Valve-regulated, nonspillable, lead acid

Qty. x Voltage x Rating

2 x 12V x7 or 7.2 AH

 

3 x 12V x 7 or 7.2 AH

Batt. Mfg./ Part #

CSB GP1270F2 or Panasonic LC-R127R2CH1

Back-up Time

See Typical Battery Discharge Curves

Recharge Time

5 Hours to 95% capacity after full discharge into 100% load

ENVIROMENTAL

 

 

 

Operating Temperature

+32° F to +104° F (0° C to +40° C)

Storage Temperature

+5° F to +122 °F (-15° C to +50° C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to10,000 ft. (3000 m) at 40° C without derating

Storage Elevation

50,000 ft. (15,000 m) maximum

Audible Noise

<45 dBA, at 1 meter

AGENCY

 

 

 

Safety

UL 1778, c-UL Listed

RFI/EMI

FCC Part 15, Subpart B, Class A

Immunity

IEEE 587 Category A

23

DISCONTINUED

PRODUCT

Image 23
Contents UPStation GXT Important Safety Instructions Introduction and System Description Inverter RECTIFIER/POWER Factor Correction PFC CircuitBattery Charger Major ComponentsDynamic Bypass BatteryDC to DC Converter MINI-TOWER/TOWER UPS Installations General InstallationRACK-MOUNT UPS Conversion and Installation RACK-MOUNT Conversion DiagramsOptional Battery Cabinets Installation Battery Cabinet Installation DiagramSerial Communications Ferrite Bead InstallationUpstation GXT On/Alarm Silence/Manual Battery Test Button Controls and IndicatorsOperation Normal Mode OperationBattery Recharge Mode Battery Mode OperationPIN Assignmentcollector to Emiter Communications Interface PortUPS Monitoring UPS Intellislot Communications MaintenanceUPS Intelligent Communications For 700/1000 VA MINI-TOWER Models Battery Replacement ProceduresRACK/TOWER Models For 1000 to 3000 VA RACK/TOWER Models Tower Models onlyRack / Tower Battery Replacement Internal Battery minutes Upstation GXT Battery RUN TimesAudible Alarm Conditions Fuse Replacement ProceduresTroubleshooting Problem Cause Solution Troubleshooting GuideVA/W SpecificationsGXT1000RT-120 GXT1000RTE-120 Weight kg lbs Used w/ UPS Model Battery Cabinet SpecificationsLimited Warranty 700-3000 VA 120