1.4 Mimic Indications

S1 Healthy S1 Priority S1 Feeding

Priority

Selection

Switch

Load on S1

Load on Super Switch Load on S2

Unsynchronised transfer

S2 Healthy S2 Priority S2 Feeding

Fig 1.4 – Mimic and LED Indications

LED INDICATION

Mimic indications: Ten LEDs are mounted on the mimic plate;

Glowing LED’s indicate the status of the Network Power Switch.

S1

Healthy:

Source –1 is a healthy source and is well above the 10% under voltage setting.

S2

Healthy:

Source –2 is a healthy source and is well above the 10% under voltage setting.

S1

Priority:

The priority selector switch is on S1 priority position.

S2

Priority:

The priority selector switch is on S2 priority position.

S1

Feeding:

The load is fed through source –1.

S2

Feeding:

The load is fed through source -2.

Overload:

Overload has occurred i.e. current level crossed 110% of full load.

Unsynchronized:

The sources are out of phase-synchronized window.

Load on S1:

Source –1 is feeding the load.

Load on S2:

Source –2 is feeding the load.

Page 1-4

Image 14
Contents Network Power Switch Emerson Network Power Dear CustomerEnglish Page Registered Head Office Branch Offices Conformity and Standards Table of Contents This manual describes the following equipment Equipment Part NumberPage General description IntroductionDesign Concept Mechanical Design Description Mimic Indications LED IndicationManual Bypass Switch Operation Manual Bypass Switch OperationPotential free contacts Operating Instructions General NotesSwitching the Load to Manual Bypass condition Switch to Yellow LED ‘ON’ Position onlyInstallation Procedure Equipment positioning and environmental considerationsConnecting cables to Network Power Switch Cable entryCable connections Network Power Switch Electrical Specifications SpecificationsGeneral Specifications Mechanical specifications Environmental specificationsNetwork Power Switch Page4-3 Page Installation Drawings Power Circuit Diagram External Power Cable Connections 431 mm Network Power Switch 02/04