Liebert 110V manual General Specifications, Electrical Specifications

Page 23

User Manual

Chapter 3 – Installation Procedure

Network Power Switch

4 Chapter 4 - Specifications

4.1General Specifications

Manual and Automatic Transfers

Sense and transfer time – less than 6 milliseconds

Break-Before make switching

Selectable preferred source

Selectable auto/manual retransfer

In-phase transfer window – adjustable from 5 ± 1°

Convection cooling

Hot swappable electronic static switching module

Live mimic on Hot swappable unit for indicating load supply status & alarms

Make before break manual bypass switch to transfer load from static switch to direct source 1 or source 2

4.2Electrical Specifications

 

ELECTRICAL

 

UNITS

DESCRIPTION

 

CHARACTERISTICS

 

 

 

 

 

 

 

 

 

 

 

Nominal Input Voltage

 

Volts

110, 115 or 120 volts singe phase, 3W+G, 50 Hz. Solidly grounded

 

 

 

 

power sources

 

Nominal Output current

 

Amps

25

 

 

 

 

 

 

Frequency

 

Hz

50 / 60

 

 

 

 

 

 

Source unhealthy status

 

-

Guaranteed Transfer to alternate source within –15 % of Vnominal

 

 

 

 

 

 

Load Power factor range

 

-

0.5 to unity leading or lagging

 

 

 

 

 

 

Load Crest factor

 

-

upto 3.5

 

 

 

 

 

 

In-Phase transfer window

 

-

Adjustable from 5 ± 1º

 

 

 

 

 

 

Source voltage distortion

 

%

up to 10% THD

 

 

 

 

 

 

Overload capability

 

%

125% of continuous current for 2 hrs, 1000% for two cycles minimum.

 

 

 

 

 

 

Over current Protection

 

-

By semi conductor fuse

 

 

 

 

 

 

Short circuit withstand

 

Amps

upto 20,000 symmetrical amps, protected by internal fusing.

 

capability

 

 

 

 

 

 

 

 

 

 

 

Redundant Control Power

 

-

taken from available source 1 and source 2

 

supplies

 

 

 

 

 

 

 

 

 

 

 

Integral Maintenance Bypass

 

-

Make before break operation

 

 

 

 

 

 

Alarm contacts

 

-

Eight Isolated Normally Open alarm & static switch Status contacts.

 

 

 

 

 

 

Unsynchronised transfer

 

 

6 milllisec for synchronized transfer and 16 millisec for unsynchronized

 

 

 

transfer.

 

 

 

 

 

 

 

 

 

Page4-1

Image 23
Contents Network Power Switch Dear Customer Emerson Network PowerEnglish Page Registered Head Office Branch Offices Conformity and Standards Table of Contents Equipment Part Number This manual describes the following equipmentPage Introduction General descriptionDesign Concept Mechanical Design Description LED Indication Mimic IndicationsManual Bypass Switch Operation Manual Bypass Switch OperationPotential free contacts General Notes Operating InstructionsSwitch to Yellow LED ‘ON’ Position only Switching the Load to Manual Bypass conditionEquipment positioning and environmental considerations Installation ProcedureCable entry Connecting cables to Network Power SwitchCable connections Network Power Switch Electrical Specifications SpecificationsGeneral Specifications Environmental specifications Mechanical specificationsNetwork Power Switch Page4-3 Page Installation Drawings Power Circuit Diagram External Power Cable Connections 431 mm Network Power Switch 02/04