Chapter 1 - General Description

Network Power Switch

1.5 Manual Bypass Switch Operation

BYPASS ON S1 SOURCE

YELLOW LED (LOAD ON S1)

OUTPUT

YELLOW LED (LOAD ON S2)

BYPASS ON S2 SOURCE

Fig 1.5 – Manual Bypass Switch Operation

Manual Bypass switch is used only when a fault occurs in the Network Power Switch and the control circuitry of the Network Power Switch is to be checked. For doing this operation the load is connected to the bypass. For Normal Operation, the position of the switch should be at Network Power Switch output position (i.e. horizontal)

If the load is to be fed through the source 1 Bypass, first it is to be unlocked and the knob should be rotated upwards. To feed through source 2 bypass the knob is to be rotated downward.

A mechanical interlocking arrangement is provided on this Bypass switch, by which the Hot swappable unit can be removed only when load is connected to bypass. In normal operation when the load is connected to Network Power Switch, the Hot swappable unit cannot be removed.

Operating Network Power Switch in Normal Mode (load connected to Network Power Switch output)

Unlock the Manual Bypass Switch with the key provided.

Depending upon the available healthy source (i.e. either Source-1 or Source-2 ) select it by changing the Manual Bypass Switch position.

Unlock the sliding module

Pull out the Hot swappable sliding module out of the Network Power Switch, which contains (SCR assembly, control circuitry).

Operating Network Power Switch in Bypass mode

Insert the Hot swappable module into the Network Power Switch unit

Lock the sliding module for preventing its accidental opening.

Unlock the Manual Bypass Switch with the key provided

Connect the Load output to Network Power Switch by changing the switch position to Network Power Switch output.

Depending on the priority switch, Load will get transferred to source-1, if the priority switch is on source1.

The Static Switch output position LED will glow

Page1-5

Image 15
Contents Network Power Switch Dear Customer Emerson Network PowerEnglish Page Registered Head Office Branch Offices Conformity and Standards Table of Contents Equipment Part Number This manual describes the following equipmentPage Introduction General descriptionDesign Concept Mechanical Design Description LED Indication Mimic IndicationsManual Bypass Switch Operation Manual Bypass Switch OperationPotential free contacts General Notes Operating InstructionsSwitch to Yellow LED ‘ON’ Position only Switching the Load to Manual Bypass conditionEquipment positioning and environmental considerations Installation ProcedureCable entry Connecting cables to Network Power SwitchCable connections Network Power Switch Specifications General SpecificationsElectrical Specifications Environmental specifications Mechanical specificationsNetwork Power Switch Page4-3 Page Installation Drawings Power Circuit Diagram External Power Cable Connections 431 mm Network Power Switch 02/04