C5.1 UL Requirements
The following must be adhered to in order to conform to UL requirements:
1.Minimum 18 AWG cable for connection to a Centralized DC power source.
2.Minimum 14 AWG cable for connection to earthing wiring.
3.Use only with Listed 10 A circuit breaker provided in building installation.
4.“Complies with FDA radiation performance standards, 21 CFR subchapter J.” or equivalent.
5.Fastening torque of the lugs on the terminal block: 9 inch pound max.
6.Centralized DC Power Source cable securement, use at least four cable ties to secure the cable to the rack at least 4 inches apart with the first one located within 6 inches of the terminal block.