GE GFK-0726B Chapter Troubleshooting, Status LED is not on Steady, Serial Communication Problems

Page 16

Chapter

3

Troubleshooting

This chapter provides procedures for diagnosing State Logic Processor (SLP) problems. If these procedures do not solve the problem, contact the GE Fanuc Hotline (1-800-828-5747) for assistance.

Status LED is not ON Steady

1.Check that power is supplied to the I/O rack housing the SLP. Try removing and reinstalling the SLP.

2.Cycle power to the SLP, then press the reset button for more than 5 seconds.

3.Turn the power OFF and disconnect the battery and short the SLP battery terminal connection points to clear the SLP. Reconnect the battery, turn ON power again, and reset the SLP.

4.Check that the CPU is functioning properly by checking its ªOKº LED.

5.Check that there are no empty slots between the CPU and the SLP. If there are empty slots, the Status LED blinks continuously.

6.If the Status LED is still not ON, try to download a program from ECLiPS or OnTOP. If you can connect with the SLP and download a program, then the Status LED is faulty.

7.If you get a message that ECLiPS or OnTOP cannot connect to the controller, then check the fault table in the CPU using Logicmaster 90. If there is a fault ªBad or missing moduleº, then the SLP is faulty and must be returned for repairs.

8.If there is no fault then contact the GE Fanuc Hotline for assistance.

Serial Communication Problems

This section is split into two parts, communication problems to ECLiPS or OnTOP and problems with other serial devices.

GFK-0726B

3-1

Image 16
Contents GE Fanuc Automation GFL±002 GE Fanuc Automation North America, Inc Page Content of this Manual We Welcome Your Comments and SuggestionsContents SampleLogicmasterConfigurationScreen Contents Chapter State Logic Processor Description Physical Description GFK-0726BSeries 90-30 State Logic Processor Operational Description Selecting the Right Slot Chapter Installation and MaintenanceInserting the SLP Configuration Sample Logicmaster Configuration ScreenBattery Serial Communication Problems Chapter TroubleshootingStatus LED is not on Steady Communications Problems with ECLiPS or OnTOP Communications Problems with Another Serial DeviceChapter SerialCommunications Programming Serial Communications Programmable Setup Options Serial Port SetupECLiPSor OnTOP Options Serial Port Parameters Serial Cable Mini Converter KitOther Cable Options RTS CTS DTR GND PCMNo Connection Signal Ground Custom Made CablesWYE Cable Connections for Series 90-30 SLP Chapter Specifications HardwareSpecificationsSLP I/O and Register Specifications Firmware Specifications