Fortinet 5140-R manual Connecting the FortiGate-5140 chassis to data center ground

Page 19

Power connection and configuration

To connect a FortiGate-5140 PEM to data center DC power

1Attach the ESD wrist strap to your wrist and to an ESD socket or to a bare metal surface on the chassis or frame.

2Loosen the screws and remove the terminal block cover from the FortiGate-5140 PEM.

3Connect the DC power wires (see Figure 9):

Connect a black -48V power wire from the data center DC power source to connector 1 on the FortiGate-5140 PEM terminal strip labeled -48V/-60 VDC nom.

Connect a black -48V power wire from the data center DC power source to connector 2 on the FortiGate-5140 PEM terminal strip labeled -48V/-60 VDC nom.

Connect a black -48V power wire from the data center DC power source to connector 3 on the FortiGate-5140 PEM terminal strip labeled -48V/-60 VDC nom.

Connect a black -48V power wire from the data center DC power source to connector 4 on the FortiGate-5140 PEM terminal strip labeled -48V/-60 VDC nom.

Connect a red RTN return wire from data center RTN to connector 1 on the FortiGate-5140 PEM terminal strip labeled RTN.

Connect a red RTN return wire from data center RTN to connector 2 on the FortiGate-5140 PEM terminal strip labeled RTN.

Connect a red RTN return wire from data center RTN to connector 3 on the FortiGate-5140 PEM terminal strip labeled RTN.

Connect a red RTN return wire from data center RTN to connector 4 on the FortiGate-5140 PEM terminal strip labeled RTN.

4Secure the power cabling to the chassis using tie wraps and the back cable tray.

5If required, label the black wires -48V.

6If required, label the red wires RTN.

7Re-attach the terminal block cover to the FortiGate-5140 PEM.

Connecting the FortiGate-5140 chassis to data center ground

The FortiGate-5140 chassis includes a ground terminal on the lower left side of the FortiGate-5140 back panel (see Figure 2 on page 7). The shelf ground terminal provides two M6 bolts to connect a double-lug ground terminal cable. This connector must be connected to data center ground.

You need the following tools and equipment to connect the FortiGate-5140 chassis to ground:

A number 2 Phillips screwdriver.

An electrostatic discharge (ESD) preventive wrist or ankle strap with connection cord.

One green AWG-6 stranded wire with terminal lug with 45° angle tongue attached.

FortiGate-5140-R Chassis Guide

 

01-30000-87705-20090108

19

http://docs.fortinet.com/ Feedback

 

Image 19
Contents FortiGate-5140-R FortiGate-5140-R Chassis Guide Contents Comments on Fortinet technical documentation For more informationFortiGate-5140 chassis Slot FortiGate-5140 chassis front panelSlot numbers FortiGate-5140 chassis back panelFortiGate-5140 shelf managers Physical description of the FortiGate-5140 chassisLED Shelf Manager fan and power control FortiGate-5140 shelf alarm panelSerial Shelf alarm panel telco alarmsConnecting to the shelf manager CLI using a serial port Shelf manager command line interface CLITo add or change the shelf manager root account password FortiGate-5140 Shelf Alarm PanelAir filter To use the shelf manager command line interface agent CliaCooling fan tray front panel Cooling fan traysCooling fan trays About data center DC power Power connection and configurationTerminal strip Connectors Connecting a FortiGate-5140 PEM to data center DC power48V/-60 VDC nom RTN positive To connect a FortiGate-5140 PEM to data center DC power Connecting the FortiGate-5140 chassis to data center groundTo connect the FortiGate-5140 chassis to data center ground ConnectorLED FortiGate-5053 power converter tray front and back panel48V Redundant FortiGate-5140 power supplies Basic power requirementsRedundant FortiGate-5053 power converter trays Redundant FortiGate-5053 power converter trays+ 1 redundancy 48V/-60 VDC RTN positive Terminal strip Connectors Wiring the FortiGate-5053 power converter tray Turning on FortiGate-5140 chassis powerTurning on FortiGate-5140 chassis power Inserting 5000-series modules into a FortiGate-5140 chassis Mounting the FortiGate-5140 chassisAir flow FortiGate-5140 hardware procedures Fortinet documentation Customer service and technical supportRegister your Fortinet product Vcci