Fortinet 5140-R manual FortiGate-5140 shelf alarm panel, Shelf Manager fan and power control

Page 10

FortiGate-5140 shelf alarm panel

FortiGate-5140 chassis

Shelf Manager fan and power control

The FortiGate-5140 shelf managers monitor the internal temperature of the FortiGate-5140 chassis and adjust the operating speed of the FortiGate-5140 chassis cooling fans as required.

When the chassis is first powered on all cooling fans run at full speed. Once the shelf manager is up and running, the shelf manager reduces cooling fan speeds to maintain an optimum temperature in the chassis. If shelf managers are not installed or not operating correctly the FortiGate-5140 chassis cooling fans always operate at full speed.

FortiGate-5140 shelf alarm panel

The FortiGate-5140 shelf alarm panel (SAP), located at the top of the FortiGate-5140 front panel, provides LED indicators of FortiGate-5140 alarms, a telco alarm connector, an alarm LED reset button, and console access to the FortiGate-5140 shelf managers. The LED alarm indicators include critical, major, and minor alarms as well as three user defined alarms.

The alarm LED reset button (RESET) on the shelf alarm panel activates the Alarm Cutoff (ACO) state. When ACO is activated, the active alarm LEDs blink and all of the alarm relays are deactivated.

Figure 4: FortiGate-5140 shelf alarm panel front panel

Minor Alarm (Amber)

 

 

 

 

 

 

 

 

User 1 Alarm (Amber)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Major Alarm (Red)

 

 

 

 

 

 

 

 

 

 

User 2 Alarm (Amber)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Critical Alarm (Red)

 

 

 

 

 

 

 

 

 

 

User 3 Alarm (Amber)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5140SAP

 

 

 

 

 

 

 

 

SERIAL 1

SERIAL 2

 

ALARM

 

 

 

 

 

 

 

 

 

CAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

CRITI MAJORMINOR USER1 USER2 USER3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retention

Alarm

SERIAL 1 (Primary

 

 

 

Telco

Alarm

Retention

Screw LED Reset

 

Shelf Manager)

 

 

 

 

Interface

Screw

 

 

 

Button

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERIAL 2 (Secondary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shelf Manager)

 

 

 

Table 3: FortiGate-5140 shelf alarm panel LEDs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED

 

State

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRITICAL

 

Off

Normal operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red

Indicates a critical alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking

Alarm cutoff (ACO) activated by pressing the alarm LED reset button.

 

 

 

 

Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAJOR

 

Off

Normal operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red

Indicates a major alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking

Alarm cutoff (ACO) activated by pressing the alarm LED reset button.

 

 

 

 

Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINOR

 

Off

Normal operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amber

Indicates a minor alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking

Alarm cutoff (ACO) activated by pressing the alarm LED reset button.

 

 

 

 

Amber

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

USER1

 

Off

Normal operation

 

 

 

 

 

 

 

 

USER2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amber

Indicates a user-definable alarm.

 

 

 

USER3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking

Alarm cutoff (ACO) activated by pressing the alarm LED reset button.

 

 

 

 

Amber

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FortiGate-5140-R Chassis Guide

1001-30000-87705-20090108http://docs.fortinet.com/ Feedback

Image 10
Contents FortiGate-5140-R FortiGate-5140-R Chassis Guide Contents For more information Comments on Fortinet technical documentationFortiGate-5140 chassis FortiGate-5140 chassis front panel SlotFortiGate-5140 chassis back panel Slot numbersPhysical description of the FortiGate-5140 chassis FortiGate-5140 shelf managersLED FortiGate-5140 shelf alarm panel Shelf Manager fan and power controlShelf alarm panel telco alarms SerialShelf manager command line interface CLI Connecting to the shelf manager CLI using a serial portFortiGate-5140 Shelf Alarm Panel To add or change the shelf manager root account passwordTo use the shelf manager command line interface agent Clia Air filterCooling fan trays Cooling fan tray front panelCooling fan trays Power connection and configuration About data center DC powerTerminal strip Connectors Connecting a FortiGate-5140 PEM to data center DC power48V/-60 VDC nom RTN positive Connecting the FortiGate-5140 chassis to data center ground To connect a FortiGate-5140 PEM to data center DC powerConnector To connect the FortiGate-5140 chassis to data center groundFortiGate-5053 power converter tray front and back panel LED48V Basic power requirements Redundant FortiGate-5140 power suppliesRedundant FortiGate-5053 power converter trays Redundant FortiGate-5053 power converter trays+ 1 redundancy 48V/-60 VDC RTN positive Terminal strip Connectors Turning on FortiGate-5140 chassis power Wiring the FortiGate-5053 power converter trayTurning on FortiGate-5140 chassis power Inserting 5000-series modules into a FortiGate-5140 chassis Mounting the FortiGate-5140 chassisAir flow FortiGate-5140 hardware procedures Fortinet documentation Customer service and technical supportRegister your Fortinet product Vcci