Falcon SG2K-1T-HW, SG3K-2T-HW, SG3K-1T-HW, SG2K-2T-HW 2KVA- 3KVA UPS Models = 150.0 lbs, 68kg

Page 11

5.Select a suitable location for the UPS near enough to the computer or equipment to to be protected. Connect the power cord(s) for the equipment to be protected to the UPS output receptacles.

VERIFY THE TABLE OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE

WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.

2KVA- 3KVA UPS MODELS = 150.0 lbs, (68kg)

6.If extended battery banks are to be connected to the UPS, please refer to page 8 for further instructions.

7.If unattended computer shutdown and monitoring are desired, connect the green UPS/Computer cable to the DB-9 connector located on the UPS rear panel. Then install the shutdown and monitoring software provided with the UPS. For your reference, UNIX shutdown and monitoring software is available from Falcon Electric at an additional cost.

8.Verify the location selected has adequate ventilation to allow for the proper cooling of the UPS.

DO NOT BLOCK UPS FANS OR AIR VENTS. THE UPS MUST NOT BE INSTALLED IN AN ENCLOSED AREA.

9.Turn the input circuit breaker located on the UPS rear panel to the “on” position. The internal UPS fan and front panel "line" indicator should turn on, followed by the "bypass" LED, and after several seconds, the "inverter" LED.

10.Turn on the connected equipment and verify the UPS does not go into overload by observing the front panel load indicator LEDs.

11.The UPS, optional external battery bank(s) and additional chargers should be installed and turned on for 24 hours to charge the batteries. During this initial 24 hour charging period, battery backup time may be substantially reduced.

IMPORTANT

TO TURN OFF THE UPS.

1.SWITCH OFF THE INPUT CIRCUIT BREAKER LOCATED ON THE UPS REAR PANEL.

2.PRESS THE ON/OFF BUTTON LOCATED ON THE UPS FRONT PANEL UNTIL THE UPS BEEPS.

3.THE UPS WILL CONTINUE TO OPERATE FOR ABOUT 30 SECONDS AND THEN SHUTDOWN.

DO NOT PRESS THE ON/OFF BUTTON OR TURN THE CIRCUIT BREAKER ON AGAIN DURING THE SHUTDOWN PROCESS OR THE UPS WILL GO TO AN ALARM CONDITION, WARNING THAT THE UPS WAS NOT SHUTDOWN PROPERLY.

SHOULD THIS OCCUR, TURN OFF THE INPUT CIRCUIT BREAKER AGAIN AND WAIT UNTIL THE UPS SHUTS DOWN.

9

Image 11
Contents SG2K-1T-HW SG2K-2T-HW SG3K-1T-HW SG3K-2T-HW Owners Operating ManualTable of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions General Common for all models ChapterSelect a suitable location for the UPS SW1 SG3K-2T-HW Model RequiredDo not USE the Upper Terminal Connections Terminal Wiring DesignationsUPS Output Requirements UPS Startup 2KVA- 3KVA UPS Models = 150.0 lbs, 68kg Typical Extended Battery Bank & UPS Interconnection Installation Procedure for Extended Battery BanksFor 2KVA -HW Models SG 2-3kVA Tower Extended Battery Bank Selection GuideOperation Load Level Indicator LedsInverter Indicator LED = UPS Output Voltage is of Range Audible AlarmsCategory one alarms Category two alarmsSG2K-1T-HW & SG3K-1T-HW Typical Rear Panel Overview Battery Fuse HolderSupported Protocols Communications InterfacesLocation Typical Falcon Dry Contact Relay Board No on-bypass signalWith on-bypass signal Opto Board Internal Circuitry No-bypass signalTypical Falcon Opto-coupler Interface Card APC Style Board APC Style Dry Contact Relay BoardBattery Replacement Care & MaintenanceBattery Life vs. Temperature FCC Considerations Storing the UPS and Batteries800.842.6940 Falcon Web Support Technical SupportRequesting Technical Information or Support SUPPORT@FALCONUPS.COMGeneral Provisions Limited NEW Product Warranty AgreementSG SeriesTM UPS Plus