5.BYPASS INDICATOR LED

When this LED is lit the UPS bypass is active. Should the Alarm LED be lit at the same time, the UPS detected an internal failure and the UPS must be serviced.

6.INVERTER INDICATOR LED

When this LED is lit, the UPS inverter is operating and powering the connected load.

7.GREEN MODE LED INDICATOR

This LED is lit when the connected output load of the UPS drops to under 10% of the full rated output of the UPS, providing SW3 is in the "down" position (Green Mode Enabled) as shown on page 7. The UPS is automatically set to bypass mode and the inverter is turned off, reducing the power requirement. NO BATTERY BACKUP IS PROVIDED IN THIS MODE. (The UPS is shipped from the factory with SW3 in the "up" or disabled position.)

8.OVER CREST INDICATOR LED

This LED lights when the connected load getting close to the peak current rating of the UPS.

9.ALARM INDICATOR LED

This LED is lit during the following conditions:

a.The inverter voltage is too high or low.

b.UPS over-temperature condition.

c.The battery voltage is too high.

d.The internal DC Bus has an under or over voltage condition.

e.The internal microprocessor or memory failure.

10.ON / OFF BUTTON

The following describes the different modes of operation for this button:

a.Depressing this button when the UPS is off, and the utility voltage is not present, or with the UPS input circuit breaker in the off position, will cause the UPS to DC start and run on internal battery until the ON/OFF button is depressed again.

b.Pressing this button while the UPS is on, and utility is present, will place the UPS into bypass mode.

c.Pressing this button when with the UPS input circuit breaker off, or when the utility voltage is not present, will turn off the UPS.

TO TURN UPS ON: CONNECT THE UPS TO UTILITY POWER AND TURN ON THE MAIN CIRCUIT BREAKER LOCATED ON THE REAR PANEL. DO NOT PRESS THE “ON” BUTTON LOCATED ON THE FRONT PANEL OR THE UPS WILL BE PLACED INTO BYPASS MODE.

TO TURN UPS OFF: TURN OFF THE MAIN CIRCUIT BREAKER LOCATED ON THE REAR PANEL AND DEPRESS THE "ON/OFF" BUTTON UNTIL THE UPS BEEPS AND WAIT FOR THE UPS TO SHUTDOWN AND TURN OFF (ABOUT 30 SECONDS).

11.TEST BUTTON

The following describes the different modes of operation for this button:

a.Pressing the Test button while in Green Mode will disable Green Mode.

b.Pressing the Test button while utility is present will put the UPS through a self test diagnostic.

c.Pressing the Test button while in battery mode will turn the battery Audible alarm off. Depressing it again will turn the Audible alarm back on.

13

Image 15
Contents SG2K-1T-HW SG2K-2T-HW SG3K-1T-HW SG3K-2T-HW Owners Operating ManualTable of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions General Common for all models ChapterSelect a suitable location for the UPS SW1 SG3K-2T-HW Model RequiredTerminal Wiring Designations UPS Output RequirementsDo not USE the Upper Terminal Connections UPS Startup 2KVA- 3KVA UPS Models = 150.0 lbs, 68kg Typical Extended Battery Bank & UPS Interconnection Installation Procedure for Extended Battery BanksFor 2KVA -HW Models SG 2-3kVA Tower Extended Battery Bank Selection GuideOperation Load Level Indicator LedsInverter Indicator LED = UPS Output Voltage is of Range Audible AlarmsCategory one alarms Category two alarmsSG2K-1T-HW & SG3K-1T-HW Typical Rear Panel Overview Battery Fuse HolderCommunications Interfaces LocationSupported Protocols No on-bypass signal With on-bypass signalTypical Falcon Dry Contact Relay Board No-bypass signal Typical Falcon Opto-coupler Interface CardOpto Board Internal Circuitry APC Style Board APC Style Dry Contact Relay BoardCare & Maintenance Battery Life vs. TemperatureBattery Replacement FCC Considerations Storing the UPS and Batteries800.842.6940 Falcon Web Support Technical SupportRequesting Technical Information or Support SUPPORT@FALCONUPS.COMGeneral Provisions Limited NEW Product Warranty AgreementSG SeriesTM UPS Plus