Falcon SG2K-2T-HW, SG3K-2T-HW, SG3K-1T-HW Communications Interfaces, Location, Supported Protocols

Page 18

CHAPTER 5

COMMUNICATIONS INTERFACES

RS-232 INTERFACE

Location:

The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector.

Supported Protocols

UPSILON 2000 & SEC Smart Mon

BAUD RATE -------

2400bps

DATA LENGTH----

8 bits

STOP BIT-----------

1 bit

PARITY--------------

None

1

2

6

TX

GND

3

7

GEN

4

8

RX

 

 

59

DB-9 Connector Pin Assignment

Pin #

Function explanation

I/O

9

RS 232 Rx

INPUT

6

RS 232 Tx

OUTPUT

7

Ground

 

 

 

 

 

 

 

CAUTION

When making a connection between a computer and the UPS RS-232 port, always use the green cable supplied with the UPS.

CAUTION

There are communications options that WILL DISABLE the RS-232 port and render it inoperable. The options are as follows:

a.Internal SNMP/HTTP agent option installed into the UPS communications option slot.

The following options WILL NOT affect the operation of the RS-232 port:

a.Falcon Opto Coupler based signal interface board installed to the communications option slot.

b.Any Falcon relay based, dry contact signal interface board installed into the communications option slot.

CAUTION

DB-9 Signals are not isolated and intended for connection to like RS-232 interfaces. DO NOT APPLY ANY OTHER VOLTAGES TO THESE PINS!

16

Image 18
Contents Owners Operating Manual SG2K-1T-HW SG2K-2T-HW SG3K-1T-HW SG3K-2T-HWTable of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Chapter General Common for all modelsSelect a suitable location for the UPS SW1 Model Required SG3K-2T-HWTerminal Wiring Designations UPS Output RequirementsDo not USE the Upper Terminal Connections UPS Startup 2KVA- 3KVA UPS Models = 150.0 lbs, 68kg Installation Procedure for Extended Battery Banks Typical Extended Battery Bank & UPS InterconnectionSG 2-3kVA Tower Extended Battery Bank Selection Guide For 2KVA -HW ModelsLoad Level Indicator Leds OperationInverter Indicator LED Category two alarms Audible AlarmsCategory one alarms = UPS Output Voltage is of RangeBattery Fuse Holder SG2K-1T-HW & SG3K-1T-HW Typical Rear Panel OverviewCommunications Interfaces LocationSupported Protocols No on-bypass signal With on-bypass signalTypical Falcon Dry Contact Relay Board No-bypass signal Typical Falcon Opto-coupler Interface CardOpto Board Internal Circuitry APC Style Dry Contact Relay Board APC Style BoardCare & Maintenance Battery Life vs. TemperatureBattery Replacement Storing the UPS and Batteries FCC ConsiderationsSUPPORT@FALCONUPS.COM Technical SupportRequesting Technical Information or Support 800.842.6940 Falcon Web SupportLimited NEW Product Warranty Agreement General ProvisionsSG SeriesTM UPS Plus