AUDIBLE ALARMS

Audible alarm signals are divided into two different levels of alarm status. Category one alarms represent normal or correctable operational alarms. Category two alarms are sounded in the event of abnormal operation.

1.Category one alarms:

a. Two short beeps followed by three short beeps.

Notifies the user that the SG UPS is configured with the optional battery pack and is in BATTERY MODE.

-- - - - = SG UPS IS IN BATTERY MODE

b.A continuous short beep.

The SG UPS is operating from battery and is in a LOW BATTERY operation.

-- - - - - - - = SG UPS IS IN A LOW BATTERY CONDITION

c.One long beep prior to a short beep.

The SG UPS is in an OVER LOADED, OVER CREST CONDITION. Remove some load from the UPS output to correct this condition.

--- = SG UPS IS IN OVERLOAD OR OVER CREST

d.One short beep is sounded when either the ON/OFF or TEST buttons are pressed and held. This notifies the user the associated actions have been initiated by the UPS.

-= WHEN SG UPS FRONT PANEL ON, OFF AND TEST BUTTONS ARE DEPRESSED.

e.One short beep is sounded when the SELF-TEST button has been pressed and held. This notifies the self test has been started.

-= WHEN SG UPS FRONT PANEL TEST BUTTON DEPRESSED.

2.Category two alarms:

a.Three short beeps indicate the SG UPS output voltage is out of proper operating range.

-- - = SG UPS OUTPUT VOLTAGE IS OUT OF PROPER RANGE.

b.Four short beeps indicate the SG UPS output frequency is out of proper operating range. The UPS must be repaired.

-- - - = SG UPS OUTPUT FREQUENCY IS OUT OF PROPER RANGE.

c.Five short beeps indicate the SG UPS is in an over-temperature condition. Check for proper UPS cooling fan operation or blockage.

-- - - - = SG UPS INTERNAL TEMPERATURE IS TOO HIGH.

d.Should the internal POWER UP SELF-TEST fail, the SG UPS will sound the following alarms denoting the failure mode:

* A continuous rapid beeping for about 5 seconds, then the SG UPS shuts down - The UPS output voltage is out of range.

- - - - - - - - - - - - - - - - - - - - - - - - - = UPS OUTPUT VOLTAGE IS OF RANGE.

*A continuous rapid beeping for about 2 seconds and the SG UPS shuts down - The SG UPS performed a DC start, but there is no output frequency set in the UPS memory. Plug the UPS into your local utility power and turn the UPS on to set it for your local utility power frequency.

- - - - - - - - - - = The SG UPS performed a DC start, but there is no output frequency set in memory. Connect the UPS to your local utility power and turn on the UPS. Your local utility frequency is now set into the UPS memory. The next time the UPS is DC Started, its output frequency will be set automatically.

14

Image 16
Contents Owners Operating Manual SG2K-1T-HW SG2K-2T-HW SG3K-1T-HW SG3K-2T-HWTable of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Chapter General Common for all modelsSelect a suitable location for the UPS SW1 Model Required SG3K-2T-HWUPS Output Requirements Terminal Wiring DesignationsDo not USE the Upper Terminal Connections UPS Startup 2KVA- 3KVA UPS Models = 150.0 lbs, 68kg Installation Procedure for Extended Battery Banks Typical Extended Battery Bank & UPS InterconnectionSG 2-3kVA Tower Extended Battery Bank Selection Guide For 2KVA -HW ModelsLoad Level Indicator Leds OperationInverter Indicator LED Audible Alarms Category one alarmsCategory two alarms = UPS Output Voltage is of RangeBattery Fuse Holder SG2K-1T-HW & SG3K-1T-HW Typical Rear Panel OverviewLocation Communications InterfacesSupported Protocols With on-bypass signal No on-bypass signalTypical Falcon Dry Contact Relay Board Typical Falcon Opto-coupler Interface Card No-bypass signalOpto Board Internal Circuitry APC Style Dry Contact Relay Board APC Style BoardBattery Life vs. Temperature Care & MaintenanceBattery Replacement Storing the UPS and Batteries FCC ConsiderationsTechnical Support Requesting Technical Information or SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportLimited NEW Product Warranty Agreement General ProvisionsSG SeriesTM UPS Plus