CHAPTER 2
Installation Instructions For Hardwire Models
1.0UPS Input & Output Requirements.
Note: All SG Series hardwire UPS models must be installed by a licensed electrician, in accordance with the National Electrical Code (NEC) ANSI/NFPA70 and all local regulations. It is further required that the input of SG Series hardwire UPS be wired to a building service panel incorporating a dedicated “branch rated” circuit breaker of the proper rating.
| MODEL |
|
|
| REQUIRED | |
|
|
|
|
| BRANCH RATED | |
|
|
|
| CIRCUIT BREAKER | ||
20A | ||||||
15A | ||||||
30A | ||||||
20A | ||||||
|
|
|
|
|
|
|
|
| WIRE GAUGE CHART |
|
|
| |
| MODEL | AC INPUT | AC OUTPUT(S) |
| ||
|
| 120 Vac |
| 208 | ||
|
|
|
|
|
| |
| 10 Awg. 600V | 10 Awg. 600V |
|
| N/A | |
|
| 75°C CU | 75°C CU |
|
|
|
| 12 Awg. 600V | N/A |
| 12 Awg. 600V | ||
|
| 75°C CU |
| 75°C CU | ||
|
|
|
| |||
| 10 Awg. 600V 75°C | 10 Awg. 600V |
|
|
| |
|
| CU | 75°C CU |
|
|
|
|
| 12 Awg. 600V |
|
| 12 Awg. 600V | |
|
| 75°C CU |
|
| 75°C CU |
ONLY USE WIRE WITH SOLID COPPER CONDUCTORS FOR ALL INPUT/OUTPUT/BATTERY WIRING
SCREW TORQUE SPECIFICATIONS FOR
INPUT/OUTPUT WIRING BLOCK
UPS
Wire Gauge | Torque |
| (inch pounds) |
18 - 10 Awg. | 20 |
25 - 30 |
CAUTION
To reduce the risk of fire, connect only to a circuit providing
6