Falcon SG3K-1T-HW, SG3K-2T-HW, SG2K-2T-HW UPS Output Requirements, Terminal Wiring Designations

Page 9

1.1UPS Output Requirements

Note: The outputs of the SG2K-2T-HW & SG3K-2T-HW hardwire models are not configured for 240/120Vac split-phase operation. Should a 240/120Vac split-phase output configuration be required, please contact the factory.

MODEL

RECOMMENDED

BRANCH RATED OUTPUT

 

CIRCUIT BREAKER

SG2K-1T-HW:

 

Output 1: 100, 110, 115 or 120Vac selectable, 1 phase, 2 wire plus ground

20A

SG2K-2T-HW

 

Output 1: 200, 220, 230 or 240Vac selectable, 1 phase, 2 wire plus ground

15A

SG3K-1T-HW

 

Output 1: 100, 110, 115 or 120Vac selectable, 1 phase, 2 wire plus ground

30A

SG2K-2T-HW

 

Output 1: 200, 220, 230 or 240Vac selectable, 1 phase, 2 wire plus ground

20A

 

 

1

2

3

4

5

 

 

 

 

 

 

 

 

Terminal Wiring Designations

1

- Utility L1

 

 

 

4.

UPS Output L1

2

- Utility L2 or Neutral

 

 

 

5.

UPS Output L2 or Neutral

3

- Input and Output Grounds

 

 

 

 

 

 

View of the Input/Output Hardwire Terminal Block

This terminal block is located on the UPS rear panel and shown with the access cover plates

removed.

Use only the lower terminals and wire securing screws when making wiring connections to

the UPS.

DO NOT USE THE UPPER TERMINAL CONNECTIONS

Refer to the Wire Gauge Table on Page 7 for recommended wire sizes.

Refer to the Torque Specification Table on Page 7 and tighten all 20 screws as specified. Refer to Pages 9-10 for the terminal wiring designations for your specific SG UPS model.

7

Image 9
Contents SG2K-1T-HW SG2K-2T-HW SG3K-1T-HW SG3K-2T-HW Owners Operating ManualTable of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions General Common for all models ChapterSelect a suitable location for the UPS SW1 SG3K-2T-HW Model RequiredTerminal Wiring Designations UPS Output RequirementsDo not USE the Upper Terminal Connections UPS Startup 2KVA- 3KVA UPS Models = 150.0 lbs, 68kg Typical Extended Battery Bank & UPS Interconnection Installation Procedure for Extended Battery BanksFor 2KVA -HW Models SG 2-3kVA Tower Extended Battery Bank Selection GuideOperation Load Level Indicator LedsInverter Indicator LED Category one alarms Audible AlarmsCategory two alarms = UPS Output Voltage is of RangeSG2K-1T-HW & SG3K-1T-HW Typical Rear Panel Overview Battery Fuse HolderCommunications Interfaces LocationSupported Protocols No on-bypass signal With on-bypass signalTypical Falcon Dry Contact Relay Board No-bypass signal Typical Falcon Opto-coupler Interface CardOpto Board Internal Circuitry APC Style Board APC Style Dry Contact Relay BoardCare & Maintenance Battery Life vs. TemperatureBattery Replacement FCC Considerations Storing the UPS and BatteriesRequesting Technical Information or Support Technical SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportGeneral Provisions Limited NEW Product Warranty AgreementSG SeriesTM UPS Plus