1.1UPS Output Requirements
Note: The outputs of the
MODEL | RECOMMENDED |
BRANCH RATED OUTPUT | |
| CIRCUIT BREAKER |
| |
Output 1: 100, 110, 115 or 120Vac selectable, 1 phase, 2 wire plus ground | 20A |
| |
Output 1: 200, 220, 230 or 240Vac selectable, 1 phase, 2 wire plus ground | 15A |
| |
Output 1: 100, 110, 115 or 120Vac selectable, 1 phase, 2 wire plus ground | 30A |
| |
Output 1: 200, 220, 230 or 240Vac selectable, 1 phase, 2 wire plus ground | 20A |
|
| 1 | 2 | 3 | 4 | 5 |
|
|
|
|
|
| |||||
|
| Terminal Wiring Designations | ||||||
1 | - Utility L1 |
|
|
| 4. | UPS Output L1 | ||
2 | - Utility L2 or Neutral |
|
|
| 5. | UPS Output L2 or Neutral | ||
3 | - Input and Output Grounds |
|
|
|
|
|
|
View of the Input/Output Hardwire Terminal Block
This terminal block is located on the UPS rear panel and shown with the access cover plates
removed.
Use only the lower terminals and wire securing screws when making wiring connections to
the UPS.
DO NOT USE THE UPPER TERMINAL CONNECTIONS
Refer to the Wire Gauge Table on Page 7 for recommended wire sizes.
Refer to the Torque Specification Table on Page 7 and tighten all 20 screws as specified. Refer to Pages
7